705.12(B)(2) Taps.

Where inverter output connections are made at feeders, all taps shall be sized based on 125% of the inverters output circuit current + the OCPD rating protecting the feeders as calculated in 240.21(B).
Click to Enlarge
Where inverter output connections are made at feeders, all taps shall be sized based on 125% of the inverters output circuit current + the OCPD rating protecting the feeders as calculated in 240.21(B).

Code Change Summary: New code language clarifies the existing rules on taps in relation to interconnected power source connections.

In the 2020 NEC®, the existing language on load side feeder taps was relocated and slightly reworded to provide clarity.

Section 705.12(B)(2) provides the rules on utility interactive power sources such as wind, batteries, or a PV system inverter output circuit connecting to the premises wiring system through a feeder on the load side of the service disconnect.

In the 2017 NEC®, the code language addressed “any” taps but in the 2020 NEC®, “any” was changed to “all” to make sure the code reader understands that this section applies to either existing taps with a new utility interactive power source being added, or to new taps where an existing utility interactive power source was already connected. In either case, the size of the tap conductors is affected by the current added by the additional utility interactive power source.

The size of feeder tap conductors in the above scenario is directly related to determining the amount of potential current from all sources, both utility, and the interconnected power production source.

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2020 NEC® edition of NFPA 70.

2017 Code Language:

705.15(B)(2)(2)Taps. In systems where power source output connections are made at feeders, any taps shall be sized based on the sum of 125 percent of the power source(s) output circuit current and the rating of the overcurrent device protecting the feeder conductors as calculated in 240.21(B).

2020 Code Language:

N 705.12(B)(2) Taps. Where power source output connections are made at feeders, all taps shall be sized based on the sum of 125 percent of all power source(s) output circuit current(s) and the rating of the overcurrent device protecting the feeder conductors for sizing tap conductors using the calculations in 240.21(B).

Did You Like This? Let Us Know With A Like! Thanks!

705.12(B)(2) Taps.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Where power source output connections are made at feeders, which of the following is true?

A: All taps must be made at the load end of the feeder.
B: All taps shall be sized based on the sum of 125% of all power source output circuit current and the rating of the overcurrent device protecting the feeder conductors for sizing tap conductors using the calculations in 240.21(B).
C: All taps must be made at the line end of the feeder.
D: The rating of the overcurrent device protecting the feeder conductors shall not be less than 156% of the power source output circuit.