705.12(B)(1) Feeders.

For this feeder option, an overcurrent protective device (OCPD)on the load side of the power source connection shall not be rated greater than the ampacity of the feeder.
Click to Enlarge
For this feeder option, an overcurrent protective device (OCPD)on the load side of the power source connection shall not be rated greater than the ampacity of the feeder.

Code Change Summary: Revised code language provides clarity on a power source output connection to a feeder.

In the 2020 NEC®, the previous language in 705.12(B)(2)(1) has been cleaned up and relocated to 705.12(B)(1) for simplicity.

The revised code language provides two options for making an interconnection between an alternate power source and a feeder. Either option can be used when the connection is made at a location other than the opposite end of the feeder from the primary power source overcurrent protective device (OCPD).

Options (a) and (b) in 705.12(B)(1) specifically apply to the portion of the feeder on the load side of the power source output connection (see image).

When selecting the OCPD for the primary power source feeder, Section 240.4(B) permits the next higher standard OCPD rating (above the ampacity of the conductors being protected) to be used (up to 800 amps). Standard sizes of an OCPD are shown in Table 240.6(A).

Section 240.4(B) cannot be used for the portion of the feeder on the load side of the power source output connection as shown in the image.

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2020 NEC® edition of NFPA 70.

2017 Code Language:

705.12(B)(2)(1) Feeders. Where the power source output connection is made to a feeder at a location other than the opposite end of the feeder from the primary source overcurrent device, that portion of the feeder on the load side of the power source output connection shall be protected by one of the following:

a. The feeder ampacity shall be not less than the sum of the primary source overcurrent device and 125 percent of the power source output circuit current.

b. An overcurrent device on the load side of the power source connection shall be rated not greater than the ampacity of the feeder.

2020 Code Language:

N 705.12(B)(1) Feeders. Where the power source output connection is made to a feeder, the feeder shall have an ampacity greater than or equal to 125 percent of the power-source output circuit current. Where the power-source output connection is made to a feeder at a location other than the opposite end of the feeder from the primary source overcurrent device, that portion of the feeder on the load side of the power source output connection shall be protected by one of the following:

a. The feeder ampacity shall be not less than the sum of the primary source overcurrent device and 125 percent of the power-source output circuit current.

b. An overcurrent device at the load side of the power source connection point shall be rated not greater than the ampacity of the feeder.

Did You Like This? Let Us Know With A Like! Thanks!

705.12(B)(1) Feeders.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is true when applying 705.12(B)(1)(b)?

A: An overcurrent device is NOT permitted at the load side of the power source connection point.
B: An overcurrent device at the load side of the power source connection point shall be rated greater than the feeder ampacity.
C: A power-source output connection is NOT permitted to be made to a feeder at a location other than the opposite end of the feeder from the primary source overcurrent device.