690.31(D) Direct-Current Circuits on or in Buildings.

Where inside buildings, PV system dc circuits that exceed 30 volts or 8 amperes shall be contained in metal raceways, in Type MC metal-clad cable that complies with 250.118(10), or in metal enclosures.
Click to Enlarge
Where inside buildings, PV system dc circuits that exceed 30 volts or 8 amperes shall be contained in metal raceways, in Type MC metal-clad cable that complies with 250.118(10), or in metal enclosures.

Code Change Summary: Revised code language on PV system DC circuits on or in a building.

NEC Section 690.31(D) covers the rules on DC PV circuits installed ON or INSIDE a building. The parent text in Section 690.31(D) only applies to PV system DC circuits INSIDE a building whereas 690.31(D)(1) and (2) apply to wiring methods ON or IN buildings. Those PV system DC circuits ON or INSIDE a building must comply with the additional installation requirements in 690.31(D)(1) and (D)⁠(2).

Often, PV system DC circuits are installed ON a building. Once the PV system DC circuits penetrate the roof, they are now considered INSIDE a building and additional rules must be followed.

Where INSIDE buildings, PV system DC circuits that exceed 30 volts or 8 amperes must be contained IN metal raceways, or Type MC metal-clad cable that complies with 250.118(10), or in metal enclosures.

Installing DC circuits in a metal raceway (where inside the building) provides additional protection for the PV DC circuits which can pose an additional threat since the DC arc is considerably different than an AC arc when a fault occurs.Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2020 NEC® edition of NFPA 70.

2017 Code Language:

690.31(G) Photovoltaic System Direct Current Circuits on or in a Building. Where PV system dc circuits run inside a building, they shall be contained in metal raceways, Type MC metal-clad cable that complies with 250.118(10), or metal enclosures from the point of penetration of the surface of the building to the first readily accessible disconnecting means. The disconnecting means shall comply with 690.13(B) and (C) and 690.15(A) and (B). The wiring methods shall comply with the additional installation requirements in 690.31(G)(1) through (4).

(1) Embedded in Building Surfaces. Where circuits are embedded in built-up, laminate, or membrane roofing materials in roof areas not covered by PV modules and associated equipment, the location of circuits shall be clearly marked using a marking protocol that is approved as being suitable for continuous exposure to sunlight and weather.

(2) Flexible Wiring Methods. Where flexible metal conduit (FMC) smaller than metric designator 21 (trade size ¾) or Type MC cable smaller than 25 mm (1 in.) in diameter containing PV power circuit conductors is installed across ceilings or floor joists, the raceway or cable shall be protected by substantial guard strips that are at least as high as the raceway or cable. Where run exposed, other than within 1.8 m (6 ft) of their connection to equipment, these wiring methods shall closely follow the building surface or be protected from physical damage by an approved means.

(3) Marking and Labeling Required. The following wiring methods and enclosures that contain PV system dc circuit conductors shall be marked with the wording WARNING: PHOTOVOLTAIC POWER SOURCE by means of permanently affixed labels or other approved permanent marking:

(1) Exposed raceways, cable trays, and other wiring methods

(2) Covers or enclosures of pull boxes and junction boxes

(3) Conduit bodies in which any of the available conduit openings are unused

(4) Marking and Labeling Methods and Locations. The labels or markings shall be visible after installation. The labels shall be reflective, and all letters shall be capitalized and shall be a minimum height of 9.5 mm (3/8 in.) in white on a red background. PV system dc circuit labels shall appear on every section of the wiring system that is separated by enclosures, walls, partitions, ceilings, or floors. Spacing between labels or markings, or between a label and a marking, shall not be more than 3 m (10 ft). Labels required by this section shall be suitable for the environment where they are installed.

2020 Code Language:

690.31(D) Direct-Current Circuits on or in Buildings. Where inside buildings, PV system dc circuits that exceed 30 volts or 8 amperes shall be contained in metal raceways, in Type MC metal-clad cable that complies with 250.118(10), or in metal enclosures.

Exception: PV hazard control systems installed in accordance with 690.12(B)(2)(1) shall be permitted to be provided with or listed for use with nonmetallic enclosure(s), nonmetallic raceway(s), and cables other than Type MC metal-clad cable(s), at the point of penetration of the surface of the building to the PV hazard control actuator.

Wiring methods on or in buildings shall comply with the additional installation requirements in 690.31(D)(1) and (D)(2).

(1) Flexible Wiring Methods. Where flexible metal conduit (FMC) smaller than metric designator 21 (trade size ¾ ) or Type MC cable smaller than 25 mm (1 in.) in diameter containing PV power circuit conductors is installed across ceilings or floor joists, the raceway or cable shall be protected by substantial guard strips that are at least as high as the raceway or cable. Where run exposed, other than within 1.8 m (6 ft) of their connection to equipment, these wiring methods shall closely follow the building surface or be protected from physical damage by an approved means.

(2) Marking and Labeling Required. Unless located and arranged so the purpose is evident, the following wiring methods and enclosures that contain PV system dc circuit conductors shall be marked with the wording PHOTOVOLTAIC POWER SOURCE or SOLAR PV DC CIRCUIT by means of permanently affixed labels or other approved permanent marking:

(1) Exposed raceways, cable trays, and other wiring methods

(2) Covers or enclosures of pull boxes and junction boxes

(3) Conduit bodies in which any of the available conduit openings are unused

The labels or markings shall be visible after installation. All letters shall be capitalized and shall be a minimum height of 9.5 mm (3/8 in.) in white on a red background. Labels shall appear on every section of the wiring system that is separated by enclosures, walls, partitions, ceilings, or floors. Spacing between labels or markings, or between a label and a marking, shall not be more than 3 m (10 ft). Labels required by this section shall be suitable for the environment where they are installed.

Did You Like This? Let Us Know With A Like! Thanks!

690.31(D) Direct-Current Circuits on or in Buildings.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is true of the marking requirements in 690.31(D)(2)?

A: All letters shall be capitalized and shall be a minimum height of 1/8 inch.
B: All letters shall be capitalized and shall be a minimum height of 3/8 inch in white on a red background.
C: Spacing between labels or markings, or between a label and a marking, shall not be more than 5 feet.
D: Unless located and arranged so the purpose is evident, wiring methods and enclosures that contain PV system dc circuit conductors shall be marked with the wording PV SOURCE CIRCUIT.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.