422.5 Ground-Fault Circuit-Interrupter (GFCI) Protection for Personnel.

Section 422.5 requires Class A GFCI protection for many types of appliances.
Click to Enlarge
Section 422.5 requires Class A GFCI protection for many types of appliances.

Code Change Summary: Revised code language on GFCI protection for specific appliances.

Section 210.8 provides GFCI requirements for certain receptacles and outlets whereas Section 422.5 provides GFCI protection requirements for specific appliances, whether cord-and-plug-connected or hard-wired.

In the 2020 NEC®, the GFCI requirements for specific appliances were revised to clarify that the GFCI protection must be Class A. The previous language just required GFCI protection in general which left the door open to Special Purpose GFCI devices that trip after higher levels of current leakage are detected than a Class A device. The Class A GFCI device provides the best protection for personnel and is designed to trip when between 4 mA and 6 mA of current leakage to ground is detected.

The language in item (4) was shortened up and now GFCI protection is required for all tire inflation machines rather than those only for the public.

Additional revisions now include bottle fill stations, sump pumps, and ALL dishwashers among the list of appliance types that will require GFCI protection (if operating within the voltage and current levels in the parent text of 422.5(A)). In the 2017 NEC®, only dwelling unit dishwashers required GFCI protection in accordance with 210.8(D). This language was shortened up and relocated to 422.5(A) in the 2020 NEC® and now applies to all dishwashers.

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2020 NEC® edition of NFPA 70.

2017 Code Language:

422.5(A) General. Appliances identified in 422.5(A)(1) through (5) rated 250 volts or less and 60 amperes or less, single- or 3-phase, shall be provided with GFCI protection for personnel. Multiple GFCI protective devices shall be permitted but shall not be required.

(1) Automotive vacuum machines provided for public use

(2) Drinking water coolers

(3) High-pressure spray washing machines — cord-and-plug connected

(4) Tire inflation machines provided for public use

(5) Vending machines

2020 Code Language:

422.5(A) General. Appliances identified in 422.5(A)(1) through (A)(7) rated 150 volts or less to ground and 60 amperes or less, single- or 3-phase, shall be provided with Class A GFCI protection for personnel. Multiple Class A GFCI protective devices shall be permitted but shall not be required.

(1) Automotive vacuum machines

(2) Drinking water coolers and bottle fill stations

(3) Cord-and-plug-connected high-pressure spray washing machines

(4) Tire inflation machines

(5) Vending machines

(6) Sump pumps

(7) Dishwashers

Informational Note: Section 210.8 specifies requirements for GFCI protection for the branch-circuit outlet where the covered location warrants such protection.

Did You Like This? Let Us Know With A Like! Thanks!

422.5 Ground-Fault Circuit-Interrupter (GFCI) Protection for Personnel.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Based on the 2020 NEC, which of the following is true?

A: Only commercial dishwashers require GFCI protection.
B: A three-phase sump pump is exempt from the GFCI requirements.
C: Class "A" GFCI protection for personnel is required for the appliances mentioned in 422.5(A).
D: Special Purpose GFCI devices are the same as a Class “A” GFCI device.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.