Code Change Summary: New code section addressing access to junction boxes behind a recessed luminaire.
Access to junction boxes above a hard lid ceiling has always been a major issue. Inspectors often issue red tags when a box is installed above a ceiling where the only way to reach it is to remove a light fixture.
For a service electrician, troubleshooting a circuit can be a nightmare when a box is installed above a hard lid sheetrock ceiling and no one knows it except for the original electrician who initially installed the electrical system for the building.
In the 2020 NEC®, boxes above a hard lid ceiling that are only reached by removing a luminaire are a code violation unless the box is an integral part of the luminaire.
Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2020 NEC® edition of NFPA 70.
2017 Code Language:
This code section did not exist.
2020 Code Language:
N 410.118 Access to Other Boxes. Luminaires recessed in ceilings, floors, or walls shall not be used to access outlet, pull, or junction boxes or conduit bodies, unless the box or conduit body is an integral part of the listed luminaire.
Which of the following is true regarding luminaires recessed in ceilings, floors, or walls?
| Please register or sign in for electrical continuing education courses. If you were already signed in, your session probably expired, please sign back in. |