392.30(B) Cables and Conductors.

Cable ties marked Type 2S and 21S have been evaluated for the support of cables.
Click to Enlarge
Cable ties marked Type 2S and 21S have been evaluated for the support of cables.

Code Change Summary: New requirements for cable ties used to support cables in a cable tray.

A common method used to secure and support cables in a cable tray is a cable tie or zip tie.

Not all cable ties are created equal. Some have only been evaluated to secure or position a cable. UL certifies a cable tie to UL 62275 as a “cable positioning device”.

The information listed below can be found using UL Product iQ  under product category ZODZ: (Pay close attention to the last paragraph below).

RATINGS

Type Designations for Products Investigated to ANSI/UL 62275

In the 2020 NEC®, cable ties used to support cables in a cable tray shall be listed, identified for the application and for securement and support. This aligns with similar language in other Chapter 3 articles such as 311, 320, 337, 330, 334, 348, and 393.

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2020 NEC® edition of NFPA 70.

2017 Code Language:

392.30(B) Cables and Conductors. Cables and conductors shall be secured to and supported by the cable tray system in accordance with (1), (2) and (3) as applicable:

(1) In other than horizontal runs, the cables shall be fastened securely to transverse members of the cable runs.

(2) Supports shall be provided to prevent stress on cables where they enter raceways from cable tray systems.

(3) The system shall provide for the support of cables and raceway wiring methods in accordance with their corresponding articles. Where cable trays support individual conductors and where the conductors pass from one cable tray to another, or from a cable tray to raceway(s) or from a cable tray to equipment where the conductors are terminated, the distance between the cable trays or between the cable tray and the raceway(s) or the equipment shall not exceed 1.8 m (6 ft). The conductors shall be secured to the cable tray(s) at the transition, and they shall be protected, by guarding or by location, from physical damage.

2020 Code Language:

392.30(B) Cables and Conductors. Cables and conductors shall be secured to and supported by the cable tray system in accordance with (1), (2), (3), and (4) as applicable:

(1) In other than horizontal runs, the cables shall be fastened securely to transverse members of the cable tray.

(2) Supports shall be provided to prevent stress on cables where they enter raceways from cable tray systems.

(3) The system shall provide for the support of cables and raceway wiring methods in accordance with their corresponding articles. Where cable trays support individual conductors or multiconductor cables and where the conductors or multiconductor cables pass from one cable tray to another, or from a cable tray to raceway(s) or from a cable tray to equipment where the conductors are terminated, the distance between the cable trays or between the cable tray and the raceway(s) or the equipment shall not exceed 1.8 m (6 ft). The conductors shall be secured to the cable tray(s) at the transition, and they shall be protected, by guarding or by location, from physical damage.

(4) Cable ties shall be listed and identified for the application and for securement and support.

Did You Like This? Let Us Know With A Like! Thanks!

392.30(B) Cables and Conductors.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is required when supporting cables in a cable tray?

A: Cable ties must be installed every 6 inches.
B: Cable ties must be installed at 3-foot intervals.
C: If cable ties are used, they shall be listed and identified for securement and support.
D: Cable ties are NOT permitted.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.