312.8(B) Power Monitoring or Energy Management Equipment.

These current sensors were installed to monitor the performance of this panelboard. The panelboard contained 480-volt inverter output circuits from 12 different PV inverters.
Click to Enlarge
These current sensors were installed to monitor the performance of this panelboard. The panelboard contained 480-volt inverter output circuits from 12 different PV inverters.

Code Change Summary: Revised code section now permits energy management devices inside overcurrent device enclosures.

In the 2017 NEC®, Section 312.8(B) only addressed power monitoring equipment installed inside overcurrent device enclosures such as cabinets or cutout boxes. It’s very common to see power monitoring equipment installed in panelboard cabinets and the intent of this section is to ensure that the presence of power monitoring equipment inside an enclosure doesn’t create an overcrowding issue or violate any product certifications.

In the 2020 NEC®, a public input (code change proposal) was accepted to also include energy management equipment in this section. To monitor power consumption is one thing, to manage or control the power usage is altogether different and yet both power monitoring and energy management equipment is currently available for purchase.

If installing power monitoring or energy management equipment inside a switch enclosure or other overcurrent device enclosure, the power monitoring or energy management equipment must be identified as a field installable accessory as part of a listed equipment, or must be a listed kit, evaluated for field installation in switch or overcurrent device enclosures. As well, the total area of all conductors, splices, taps, and equipment at any cross section of the wiring space cannot exceed 75 percent of the cross-sectional area of that space.

New line item 3 was added to address instrumentation and control circuits for such devices which are often between 18 AWG and 22 AWG conductors. This new section provides two options for these instrumentation or control circuits:

OR

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2020 NEC® edition of NFPA 70.

2017 Code Language:

312.8(B) Power Monitoring Equipment. The wiring space of enclosures for switches or overcurrent devices shall be permitted to contain power monitoring equipment where all of the following conditions are met:

(1) The power monitoring equipment is identified as a field installable accessory as part of the listed equipment, or is a listed kit evaluated for field installation in switch or overcurrent device enclosures.

(2) The total area of all conductors, splices, taps, and equipment at any cross section of the wiring space does not exceed 75 percent of the cross-sectional area of that space.

2020 Code Language:

312.8(B) Power Monitoring or Energy Management Equipment. The wiring space of enclosures for switches or overcurrent devices shall be permitted to contain power monitoring or energy management equipment in accordance with 312.8(B)(1) through (B)(3).

N (1) Identification. The power monitoring or energy management equipment shall be identified as a field installable accessory as part of the listed equipment or is a listed kit evaluated for field installation in switch or overcurrent device enclosures.

N (2) Area. The total area of all conductors, splices, taps, and equipment at any cross section of the wiring space shall not exceed 75 percent of the cross-sectional area of that space.

N (3) Conductors. Conductors used exclusively for control or instrumentation circuits shall comply with either 312.8(B)(3)(a) or (B)(3)(b).

(a) Conductors shall comply with 725.49.

(b) Conductors smaller than 18 AWG, but not smaller than 22 AWG for a single conductor and 26 AWG for a multiconductor cable, shall be permitted to be used where the conductors and cable assemblies meet all of the following conditions:

(1) Are enclosed within raceways or routed along one or more walls of the enclosure and secured at intervals that do not exceed 250 mm (10 in.)

(2) Are secured within 250 mm (10 in.) of terminations

(3) Are secured to prevent contact with current carrying components within the enclosure

(4) Are rated for the system voltage and not less than 600 volts

(5) Have a minimum insulation temperature rating of 90°C

Did You Like This? Let Us Know With A Like! Thanks!

312.8(B) Power Monitoring or Energy Management Equipment.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is true when installing energy management equipment inside a panelboard cabinet that contains circuit breakers?

A: The energy management equipment can only be factory installed.
B: The energy management equipment must fill the wiring space in the enclosure to at least 75%.
C: The total area of all splices, taps at any cross section of the wiring space cannot exceed 50% of the cabinet volume.
D: The total area of all equipment at any cross section of the wiring space cannot exceed 75 percent of the cross-sectional area of that space.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.