310.15(B) Ambient Temperature Correction Factors.

This raceway is several inches above the rooftop therefore no temperature adder is required.
Click to Enlarge
This raceway is several inches above the rooftop therefore no temperature adder is required.

Code Change Summary: The previous ambient temperature and rooftop correction factor tables have been renumbered.

In the 2020 NEC®, the relocation of the medium voltage conductor requirements from Article 310 to new Article 311 created a domino effect resulting in the renumbering of tables and code sections remaining in Article 310.

The above code sections and tables are pretty much the same other than a few minor changes to provide clarity and usability.

A specific change occurred in the title and text to previous Section 310.15(B)(3)(c) pertaining to raceways and cables exposed to sunlight on rooftops. The new section is 310.15(B)(2) and the title was shortened to “Rooftop”.

The language was cleaned up in 310.15(B)(2) since the previous language first provided a mandatory rule to keep raceways and cables at least 7/8 inch above the roof and then provided a way around the rule by requiring a temperature adder of 33°C (60°F) to be added to the ambient temperature when determining the overall outdoor ambient temperature for the purpose of applying correction factors.

A wiring method exposed to sunlight and very close to the roof surface will be hotter than a wiring method with a bit of distance from the rooftop. The closer the wiring method is to the roof surface; the more indirect heat is reflected back to the wiring method from the roof surface. As the wiring method gets hotter, wiring in the raceway or cable cannot continuously carry the same ampacity and must be derated.

In the 2020 NEC®, any raceways or cables exposed to direct sunlight on or above rooftops that cannot be installed at least 7/8 inch above the roof to the bottom of the raceway or cable, require a temperature adder of 33°C (60°F) to be added to the outdoor temperature to determine the applicable ambient temperature for applying the correction factors in Table 310.15(B)(1) or Table 310.15(B)(2). The requirement does not apply if type XHHW-2 insulated conductors are used.

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2020 NEC® edition of NFPA 70.

2017 Code Language:

310.15(B)(3)(c) Raceways and Cables Exposed to Sunlight on Rooftops. Where raceways or cables are exposed to direct sunlight on or above rooftops, raceways or cables shall be installed a minimum distance above the roof to the bottom of the raceway or cable of 23 mm (7∕8 in.). Where the distance above the roof to the bottom of the raceway is less than 23 mm (7∕8 in.), a temperature adder of 33°C (60°F) shall be added to the outdoor temperature to determine the applicable ambient temperature for application of the correction factors in Table 310.15(B)(2)(a) or Table 310.15(B)(2)(b).

Exception: Type XHHW-2 insulated conductors shall not be subject to this ampacity adjustment.

2020 Code Language:

N 310.15(B)(2) Rooftop. For raceways or cables exposed to direct sunlight on or above rooftops where the distance above the roof to the bottom of the raceway or cable is less than 23 mm (7∕ 8 in.), a temperature adder of 33°C (60°F) shall be added to the outdoor temperature to determine the applicable ambient temperature for application of the correction factors in Table 310.15(B)(1) or Table 310.15(B)(2).

Exception: Type XHHW-2 insulated conductors shall not be subject to this ampacity adjustment.

Did You Like This? Let Us Know With A Like! Thanks!

310.15(B) Ambient Temperature Correction Factors.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is true for type THHW wiring in a raceway installed ½ inch above a rooftop and exposed to direct sunlight?

A: 80°F must be added to the outdoor temperature for calculating the final ambient temperature correction factor.
B: 60°F must be added to the outdoor temperature for calculating the final ambient temperature correction factor for the wires.
C: 40°F must be added to the outdoor temperature for calculating the final ambient temperature correction factor.
D: 25°F must be added to the outdoor temperature for calculating the final ambient temperature correction factor.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.