250.109 Metal Enclosures.

Metal enclosures are permitted to be used to connect bonding jumpers or equipment grounding conductors, or both, together to become a part of an effective ground-fault current path.
Click to Enlarge
Metal enclosures are permitted to be used to connect bonding jumpers or equipment grounding conductors, or both, together to become a part of an effective ground-fault current path.

Code Change Summary: New code section permits a metal enclosure to serve as an effective ground-fault current path.

There are several examples in Article 250 of metal boxes and other enclosures being part of the effective ground-fault current path but until now, Article 250 has never officially recognized it.

But what about the metal box itself? Is there any language in the NEC® officially allowing a metal box or enclosure to be part of an effective ground-fault current path?

In the 2020 NEC®, metal enclosures are now permitted to be used to connect bonding jumpers or equipment grounding conductors, or both, together to become a part of an effective ground-fault current path.

There were several similar public inputs (code change proposals) this cycle to recognize metal boxes and enclosures as an “equipment grounding conductor” by adding another line item to Section 250.118. This section provides a list of fourteen different items that are considered an “equipment grounding conductor”.

The new code language was placed in a new section and was worded carefully so as not to give the impression that a metal box or enclosure is technically an “equipment grounding conductor” since not all metal boxes or enclosures are listed as grounding and bonding equipment.

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2020 NEC® edition of NFPA 70.

2017 Code Language:

This code section did not exist.

2020 Code Language:

N 250.109 Metal Enclosures. Metal enclosures shall be permitted to be used to connect bonding jumpers or equipment grounding conductors, or both, together to become a part of an effective ground-fault current path. Metal covers and metal fittings attached to these metal enclosures shall be considered as being connected to bonding jumpers or equipment grounding conductors, or both.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

250.109 Metal Enclosures.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

According to NEC 250.109, which of the following is true?

A: A metal fitting attached to a plastic enclosure is considered as being connected to bonding jumpers or equipment grounding conductors, or both.
B: A metal fitting attached to a metal enclosure is considered as being connected to the neutral conductor.
C: Metal fittings attached to a metal enclosure are considered as being connected to the grounding electrode.
D: Metal enclosures shall be permitted to be used to connect bonding jumpers or equipment grounding conductors, or both, together to become a part of an effective ground-fault current path.