210.8(E) Equipment Requiring Servicing.

Section 210.63 requires a service receptacle to be located on the same level as the heating, air-conditioning, and refrigeration equipment and no further than 25 feet. This dwelling unit attic is considered a dry location.
Click to Enlarge
Section 210.63 requires a service receptacle to be located on the same level as the heating, air-conditioning, and refrigeration equipment and no further than 25 feet. This dwelling unit attic is considered a dry location.

Code Change Summary: New code section. GFCI protection is now required for service receptacles required by Section 210.63.

NEC Section 210.63 requires a 125-volt, single-phase, 15- or 20-ampere-rated service receptacle located within 25 feet of the following:

In the 2020 NEC®, the above-mentioned service receptacle will require GFCI protection regardless of whether it is outside, inside, in an attic or in an electrical equipment room that is considered a dry location.

The committee statement regarding the addition of GFCI protection for these service receptacles expressed that the receptacles required in Section 210.63 are required specifically for the purpose of providing the maintenance worker with access to power for the use of portable tools. These receptacles are permitted to be located up to 25 feet away from the equipment requiring servicing which often results in the use of an extension cord, which can increase the hazard. For these reasons, GFCI protection will now be required for these service receptacles.

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2020 NEC® edition of NFPA 70.

2017 Code Language:

This code section did not exist.

2020 Code Language:

N 210.8(E) Equipment Requiring Servicing. GFCI protection shall be provided for the receptacles required by 210.63.

Did You Like This? Let Us Know With A Like! Thanks!

210.8(E) Equipment Requiring Servicing.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Refer to the image of HVAC equipment in a dwelling unit attic:

Based on the 2020 NEC, which of the following is true?

A: Receptacle “A” must be supplied by a 20-amp branch circuit.
B: Receptacle “A” must be supplied by a 15-amp branch circuit.
C: An HVAC service receptacle in an attic does not require GFCI protection.
D: If receptacle “A” is the required service receptacle then it must have GFCI protection.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.