Article 100 Class 1, 2 and 3 Circuits.

Class 1, 2 and 3 circuits are commonly used for remote control, signal and power limited circuits.
Click to Enlarge
Class 1, 2 and 3 circuits are commonly used for remote control, signal and power limited circuits.

Code Change Summary: The existing definitions of a Class 1, 2 and 3 circuit were relocated to Article 100.

Class 1, 2 and 3 circuits were discussed in many articles throughout previous editions of the NEC® but only defined in Article 725. Now the below definitions are found in Article 100.

Class 1 circuits can be either of the following:

Class 2 circuits are considered safe from a fire and shock initiation standpoint due to the power limitations of the Class 2 transformer or power supply.

Class 3 circuits can operate at higher voltages than a Class 2 circuit which is why a Class 3 circuit is only considered safe from a fire initiation standpoint, not shock.

See Article 725 for more on Class 1, Class 2, and Class 3 remote control, signaling, and power-limited circuits

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2020 NEC® edition of NFPA 70.

2017 Code Language:

Class 1, 2 and 3 circuits were defined only in Article 725.

2020 Code Language:

Article 100.

N Class 1 Circuit. The portion of the wiring system between the load side of the overcurrent device or power-limited supply and the connected equipment.

Informational Note: See 725.41 for voltage and power limitations of Class 1 circuits.

N Class 2 Circuit. The portion of the wiring system between the load side of a Class 2 power source and the connected equipment. Due to its power limitations, a Class 2 circuit considers safety from a fire initiation standpoint and provides acceptable protection from electric shock.

N Class 3 Circuit. The portion of the wiring system between the load side of a Class 3 power source and the connected equipment. Due to its power limitations, a Class 3 circuit considers safety from a fire initiation standpoint. Since higher levels of voltage and current than for Class 2 are permitted, additional safeguards are specified to provide protection from an electric shock hazard that could be encountered.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

Article 100 Class 1, 2 and 3 Circuits.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is true of a Class 3 circuit?

A: Due to its power limitations, it considers safety from a fire initiation standpoint and provides acceptable protection from electric shock.
B: Due to its power limitations, it considers safety only from a fire initiation standpoint.
C: It is the portion of the wiring system between the load side of the overcurrent device or power-limited supply and the connected equipment.
D: It is the portion of the wiring system on the line side of an overcurrent device.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.