230.82(3) Equipment Connected to the Supply Side of Service Disconnect.

This disconnect was installed ahead of an electric meter. It has a 200,000-amp SCCR when used with class J or R fuses. If class H or K fuses are used, it only has an SCCR of 10kA. The AFC on the line side of the switch determines which type of fuse will be needed.
Click to Enlarge
This disconnect was installed ahead of an electric meter. It has a 200,000-amp SCCR when used with class J or R fuses. If class H or K fuses are used, it only has an SCCR of 10kA. The AFC on the line side of the switch determines which type of fuse will be needed.

NEC Section 230.82 specifies all things permitted to be installed on the line side or ahead of the service disconnect. This is a dangerous location since no overcurrent protection is present ahead of the service disconnect. One of the items permitted is a meter disconnect switch.

Many utility companies require a meter disconnect switch so that the load on an electrical service can be dropped before changing or removing the electric meter. Quite often, the utility company pulls the electric meter when the building occupant fails to pay the electricity bill.

Meters are not generally designed to be pulled under load which is why a load break rated meter disconnect switch is used ahead of the meter. In order to comply with the rule in 230.82(3), the meter disconnect switch must have a short-circuit current rating (SCCR) equal to or greater than the available short-circuit current also known as the Available Fault Current (AFC).

See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on the “free access” tab and select the applicable year of NFPA 70 (National Electrical code).

2017 Code Language:

230.82 Equipment Connected to the Supply Side of Service Disconnect.

(3) Meter disconnect switches nominally rated not in excess of 1000 V that have a short-circuit current rating equal to or greater than the available short-circuit current, if all metal housings and service enclosures are grounded in accordance with Part VII and bonded in accordance with Part V of Article 250. A meter disconnect switch shall be capable of interrupting the load served. A meter disconnect shall be legibly field marked on its exterior in a manner suitable for the environment as follows: METER DISCONNECT NOT SERVICE EQUIPMENT.

2020-2023 Code Language:

230.82 Equipment Connected to the Supply Side of Service Disconnect.

(3) Meter disconnect switches nominally rated not in excess of 1000 volts that have a short-circuit current rating equal to or greater than the available fault current, if all metal housings and service enclosures are grounded in accordance with Part VII and bonded in accordance with Part V of Article 250. A meter disconnect switch shall be capable of interrupting the load served. A meter disconnect shall be legibly field marked on its exterior in a manner suitable for the environment as follows: METER DISCONNECT NOT SERVICE EQUIPMENT.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

230.82(3) Equipment Connected to the Supply Side of Service Disconnect.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Refer to the image.

How is the SCCR of the fused disconnect switch changed when different fuses are installed?

A: If class J fuses are used, it only has an SCCR of 10kA.
B: If class R fuses are used, it only has an SCCR of 10kA.
C: If class H fuses are used, it has an SCCR of 100kA.
D: If class K fuses are used, it only has an SCCR of 10kA.
Please register or sign in for electrical continuing education courses.