240.86(C) Series Ratings. Motor Contribution Exercise 1.

In order to use a series combination here, since the motor is connected between the devices that are part of the series combination, the motor full load current would not be able to exceed 1% of the AIC rating of the 10k breakers.
Click to Enlarge
In order to use a series combination here, since the motor is connected between the devices that are part of the series combination, the motor full load current would not be able to exceed 1% of the AIC rating of the 10k breakers.

When deciding to go with a series rated combination over a fully rated system, motor contribution needs to be considered if motors are located in specific locations relative to the overcurrent devices that are part of a series combination.

The reason: If a fault occurs such as a short-circuit, running motors can momentarily contribute current to the short-circuit condition (four to six times the motor full load current rating).

The additional motor contribution can result in a short-circuit current exceeding what the load side (protected) circuit breaker was tested to handle during the series rated combination testing.

NEC 240.86(C) does not allow a series rated system to be used if motors are connected between overcurrent devices used in a series combination where the sum of all motor full load current (FLC) exceeds 1% of the interrupting rating (AIC rating) of the lowest rated circuit breaker in the series combination.

See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on the “free access” tab and select the applicable year of NFPA 70 (National Electrical code).

2017 Code Language:

240.86(C) Motor Contribution. Series ratings shall not be used where

(1) Motors are connected on the load side of the higher rated overcurrent device and on the line side of the lower-rated overcurrent device, and

(2) The sum of the motor full-load currents exceeds 1 percent of the interrupting rating of the lower-rated circuit breaker.

2020 Code Language:

240.86(C) Motor Contribution. Series ratings shall not be used where

(1) Motor circuits are connected between the higher-rated overcurrent device of a series-rated combination and on the lower-rated circuit breaker, and

(2) The sum of these motor full-load currents exceeds 1 percent of the interrupting rating of the lower-rated circuit breaker.

2023 Code Language:

240.86(C) Motor Contribution. Series ratings shall not be used in the following situations:

(1) Where motor circuits are connected between the higher-rated overcurrent device of a series-rated combination and on the lower-rated circuit breaker, and

(2) Where the sum of these motor full-load currents exceeds 1 percent of the interrupting rating of the lower-rated circuit breaker.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

240.86(C) Series Ratings. Motor Contribution Exercise 1.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

What is 1% of a circuit breaker with an AIC rating of 22,000 amps?

A: 22 amps.
B: 220 amps.
C: 222 amps.
D: 1 amp.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.