Table 310.15(B)(3)(c) Ambient Temperature Adjustment for Raceways or Cables Exposed to Sunlight on or Above Rooftops.

Table 310.15(B)(3)(c) comparrison. 2011 NEC versus 2014 NEC.
Click to Enlarge
Table 310.15(B)(3)(c) comparrison. 2011 NEC versus 2014 NEC.

Code Change Summary: The title to table 310.15(B)(3)(c) has been modified to make it clear that the table now applies to more than just circular raceways on or above a roof.

In the 2011 NEC®, Table 310.15(B)(3)(c) only applied to circular raceways exposed to sunlight on or above the rooftop. Now, in the 2014 NEC®, this table applies to any raceway or cable exposed to sunlight on or above the rooftop.

Table 310.15(B)(3)(c) provides temperature adders to be added to the ambient temperature correction factors in Table 310.15(B)(2)(a) or Table 310.15(B)(2)(b). These temperature adders are based on how close a rooftop wiring method is located to the hot roof surface. The further away the wiring method is from the hot roof surface, the lower the temperature adder is.

Example: PVC coated, sunlight resistant MC cable containing THWN (75°C conductors) installed 4 in. above the rooftop in a location where the ambient temperature is 100°F.

See image for an example of Table 310.15(B)(3)(c).

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

Table 310.15(B)(3)(c) Ambient Temperature Adjustment for Raceways or Cables Exposed to Sunlight on or Above Rooftops.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

What is the required temperature adder for a rigid metal conduit installed 13 in. above the rooftop?

A: 60°F.
B: 40°F.
C: 30°F.
D: 25°F.
Please register or sign in for electrical continuing education courses.