Table 310.15(B)(3)(a) Adjustment Factors for More Than Three Current-Carrying Conductors.

Table 310.15(B)(3)(a) comparrison. 2011 NEC versus 2014 NEC.
Click to Enlarge
Table 310.15(B)(3)(a) comparrison. 2011 NEC versus 2014 NEC.

Code Change Summary: The title to table 310.15(B)(3)(a) has been modified. And the note under the table now makes it clear that the table also applies to spare conductors.

Table 310.15(B)(3)(a) provides adjustment factors when installing more than three current-carrying conductors (CCC). Previously, the table only applied when there were more than three CCC “in a raceway or cable”. Now it is clear that the adjustment factors in the table are not just required when a raceway or cable contains more than three CCC.

A good example of this is when separate cables are installed without maintaining spacing. For these installations, if cables are bundled for a continuous length longer than 24 in., the allowable ampacity of each conductor must be reduced as shown in Table 310.15(B)(3)(a).

Two more changes occurred in the note under the table:

See image for an example of Table 310.15(B)(3)(a).

Did You Like This? Let Us Know With A Like! Thanks!

Table 310.15(B)(3)(a) Adjustment Factors for More Than Three Current-Carrying Conductors.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

What is the required adjustment for 11 current carrying conductors, bundled for 36 inches without maintain spacing?

A: 80%.
B: 70%.
C: 50%.
D: 45%.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.