300.11(B) Raceways Used as Means of Support.

The class 2 thermostat cables are permitted to be secured to the EMT raceway containg power conductors for the same air conditioner.
Click to Enlarge
The class 2 thermostat cables are permitted to be secured to the EMT raceway containg power conductors for the same air conditioner.

Code Change Summary: A clarification was made to address the use of a raceway to support other wiring methods.

Generally, raceways containing conductors cannot be used to support other wiring methods. The 2011 NEC® allowed a raceway to be used to support other wiring methods if the raceway was “identified for the purpose”.

According to Article 100, identified means “recognizable as suitable for the specific purpose, function, use, environment, application, and so forth, where described in a particular code requirement”.

The new code language allows a raceway to support other wiring methods if the raceway is “identified as a means of support”.

Either way, the new code language still seems to provide no clear direction. Generally speaking, raceways are not usually identified for supporting other raceways. Here are the most common applications where a raceway can support another wiring method:

Below is a preview of the NEC®.  See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on the “free access” tab and select the applicable year of NFPA 70 (National Electrical code).

2011 Code Language:

300.11(B) Raceways Used as Means of Support. Raceways shall be used only as a means of support for other raceways, cables, or nonelectrical equipment under any of the following conditions:

(1) Where the raceway or means of support is identified for the purpose.

(2) Where the raceway contains power supply conductors for electrically controlled equipment and is used to support Class 2 circuit conductors or cables that are solely for the purpose of connection to the equipment control circuits.

(3) Where the raceway is used to support boxes or conduit bodies in accordance with 314.23 or to support luminaires in accordance with 410.36(E).

2014 Code Language:

300.11(B) Raceways Used as Means of Support. Raceways shall be used only as a means of support for other raceways, cables, or nonelectrical equipment under any of the following conditions:

(1) Where the raceway or means of support is identified as a means of support.

(2) Where the raceway contains power supply conductors for electrically controlled equipment and is used to support Class 2 circuit conductors or cables that are solely for the purpose of connection to the equipment control circuits

(3) Where the raceway is used to support boxes or conduit bodies in accordance with 314.23 or to support luminaires in accordance with 410.36(E).

Did You Like This? Follow us on Face Book! Thanks!

Electrical License Renewal Facebook Logo

300.11(B) Raceways Used as Means of Support.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

When can a raceway be used to support another non-associated wiring method?

A: When the raceway is identified for the purpose.
B: When the raceway is identified as a means of support.
C: When the non-associated wiring method is an MC cable.
D: When the non-associated wiring method is an AC cable.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.