NFPA 731 Section 4.6.3.12(2) requires raceways to be sized properly in accordance with the NEC®. Raceways, conduits and tubing are not always used with security system wiring but if they are, the raceway conduit or tubing must be sized according to the NEC®.
In the NEC®, there are two main locations (near the back of the book) used when determining the maximum number of conductors in a conduit or tubing:
There are many tables in NEC Chapter 9.
For example, Table 4 provides the dimensions and percent area for specific types of conduit and tubing. Table 5 provides dimensions of insulated conductors and fixture wires being installed in the raceway types mentioned in Table 4.
Table 5 provides dimensions of insulated conductors and fixture wires. Across the top of Table 5 from left to right are the type of wire used, the size of the wire in AWG (American Wire Gauge) or kcmil (thousands of circular mils), the approximate area and the approximate diameter.
For example, use NEC® Chapter 9 Table 5 to determine the maximum dimension for the following mixed group of insulated conductors installed in a raceway:
Refer to the image of NEC® Chapter 9 Table 5 to answer the question below.
Below is a sample of NFPA 731. For the complete section, see the actual NFPA 731 text at NFPA.ORG. Once there, click on the free access link to the latest edition of NFPA 731.
4.6.3 Wiring.
4.6.3.12 At raceway connections to junction boxes and open ends of raceways, the following shall apply:
(1) Conductors shall be protected from abrasion.
(2) Raceway shall be sized and installed in accordance with NFPA 70.
What is the total area occupied by a group of six 10 AWG type THWN conductors to be installed in a raceway?
Please register or sign in for electrical continuing education courses. If you were already signed in, your session probably expired, please sign back in. |