Article 100 Definitions. Grounded Conductor.

All neutral conductors are grounded conductors but not all grounded conductors are neutrals.
Click to Enlarge
All neutral conductors are grounded conductors but not all grounded conductors are neutrals.

A Grounded Conductor is defined as a system or circuit conductor that is intentionally grounded. When something is “grounded” in accordance with the NEC®, it is connected to ground or to a conductive body that extends the ground connection.

Some grounded conductors are also neutral conductors. A Neutral Conductor is defined as the conductor connected to the neutral point of a system that is intended to carry current under normal conditions.

Since a grounded neutral conductor is intended to carry current under normal conditions, it is required to be sized differently than an equipment grounding conductor (EGC) which is only intended to carry current during a ground-fault condition. The minimum size of a grounded conductor is determined from NEC® Table 250.102(C)(1) based on the size of the largest ungrounded service entrance conductor or equivalent area for parallel conductors.

Sometimes the load on a neutral conductor will require it to be sized larger than the bare minimum from Table 250.102(C)(1). See NEC® 220.61 for calculating the feeder or service neutral load.

For complete code sections, refer to the actual NEC® text at NFPA.ORG. Once there, click on their link to free access to the 2017 NEC® edition of NFPA 70.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

Article 100 Definitions. Grounded Conductor.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is true for a grounded conductor?

A: The size is determined from NEC Table 250.66, based on the size of the largest ungrounded service entrance conductor.
B: It is sized like an equipment bonding jumper.
C: A grounded conductor is sized from NEC Table 250.122, based on the size of the overcurrent device protecting the circuit.
D: It is intentionally grounded.
Please register or sign in for electrical continuing education courses.