Table 250.102(C)(1). Grounded Conductor, Main Bonding Jumper, System Bonding Jumper, and Supply-Side Bonding Jumper for Alternating-Current Systems.

New Table 250.102(C)(1).
Click to Enlarge
New Table 250.102(C)(1).

Code Change Summary: A new table has been added to Article 250.

Article 250 is the largest article in the NEC® and yet for years, the article has only had the following two tables:

Even though Table 250.66 is titled Grounding Electrode Conductor for Alternating-Current Systems, for many code cycles, the following items in Article 250 were all sized from the table:

In the 2014 NEC®, Table 250.66 has only one purpose; sizing the grounding electrode conductor. A new table has been added for everything else besides the grounding electrode conductor, that used to be sized from Table 250.66.

New Table 250.102(C)(1) is for sizing the grounded conductor, main bonding jumper, system bonding jumper, and supply-side bonding jumper for alternating-current systems. Note 1 under the new table contains the 12.5% rule to be used when the largest ungrounded conductor or equivalent area for parallel conductors is over 1100 kcmil copper or 1750 kcmil aluminum.

See image for an example of the new Table.

Did You Like This? Let Us Know With A Like! Thanks!

Table 250.102(C)(1). Grounded Conductor, Main Bonding Jumper, System Bonding Jumper, and Supply-Side Bonding Jumper for Alternating-Current Systems.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

What minimum size copper main bonding jumper is required at an electrical service supplied by 400 kcmil ungrounded copper service entrance conductors?

A: 4 AWG.
B: 2 AWG.
C: 1/0 AWG.
D: 2/0 AWG.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.