In the 2017 NEC®, Section 620.16(A) requires the short-circuit current rating (SCCR) to be marked on elevator control panels. There are two methods permitted in 620.16 for the required SCCR marking:
The inspector may or may not want to be responsible for allowing item 2 above since it leaves liability in the hands of the inspection agency. The informational note mentions Supplement SB in UL 508A as an example of an “approved” method. The city inspector will generally not have a copy of the standard in order to know what Supplement SB actually says.
In the 2017 NEC®, Section 620.16(B) has similar language to what is found in 409.22 for industrial control panels. Elevator control panels shall not be installed where the available short-circuit current exceeds the SCCR of the control panel, as marked in accordance with 620.16(A).
See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on the “free access” tab and select the applicable year of NFPA 70 (National Electrical code).
2014 Code Language:
620.16 The code section did not exist.
2017 Code Language:
620.16 Short-Circuit Current Rating.
(A) Marking. Where an elevator control panel is installed, it shall be marked with its short-circuit current rating, based on one of the following:
(1) Short-circuit current rating of a listed assembly
(2) Short-circuit current rating established utilizing an approved method
Informational Note: UL 508A-2013, Supplement SB, is an example of an approved method.
(B) Installation. The elevator control panel shall not be installed where the available short-circuit current exceeds its short-circuit current rating, as marked in accordance with 620.16(A).
Which of the following is true for an elevator control panel installed where the available short-circuit current is 58kA?