230.44 Cable Trays.

The label must be visible after installation and cannot be more than 10 ft. apart.
Click to Enlarge
The label must be visible after installation and cannot be more than 10 ft. apart.

Code Change Summary: New code language was added in Part III of Article 230 to specify how far apart the hazard labels must be placed to identify cable trays containing service entrance conductors.

Service entrance conductors are required by 230.70(A)(1) to be disconnected at or nearest the point where the conductors enter a building. Because of this, it’s not very often that cable trays are used to support service entrance conductors. Most of the time, cable trays do not contain service entrance conductors because cable trays are generally installed downstream of the service disconnect.

If a cable tray is in fact used to support service entrance conductors, labels are required on the cable tray so that the servicing electrician is aware that unprotected, unfused service entrance conductors are located on the cable tray. It is important to know that shutting off the service disconnect will not de-energize all conductors in the cable tray.

The 2014 NEC® requires the labels to be visible after installation and spaced no further than 10 ft. apart. The label ensures that the service entrance conductors can be traced throughout the cable tray.

Below is a preview of the NEC®.  See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on the “free access” tab and select the applicable year of NFPA 70 (National Electrical code).

2011 Code Language:

230.44 Cable Trays. Cable tray systems shall be permitted to support service-entrance conductors. Cable trays used to support service-entrance conductors shall contain only service-entrance conductors and shall be limited to the following methods:

(1) Type SE cable

(2) Type MC cable

(3) Type MI cable

(4) Type IGS cable

(5) Single thermoplastic-insulated conductors 1/0 and larger with CT rating

Such cable trays shall be identified with permanently affixed labels with the wording “Service-Entrance Conductors.” The labels shall be located so as to be visible after installation and placed so that the service-entrance conductors are able to be readily traced through the entire length of the cable tray.

2014 Code Language:

230.44 Cable Trays. Cable tray systems shall be permitted to support service-entrance conductors. Cable trays used to support service-entrance conductors shall contain only service-entrance conductors and shall be limited to the following methods:

(1) Type SE cable

(2) Type MC cable

(3) Type MI cable

(4) Type IGS cable

(5) Single conductors 1/0 and larger with CT rating

Such cable trays shall be identified with permanently affixed labels with the wording “Service-Entrance Conductors.” The labels shall be located so as to be visible after installation with a spacing not to exceed 3 m (10 ft) so that the service-entrance conductors are able to be readily traced through the entire length of the cable tray.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

230.44 Cable Trays.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following labels is correct for a cable tray supporting service entrance conductors?

A: “Service-Entrance Conductors” every 10 ft.
B: “Service Conductors” every 10 ft.
C: “Service-Entrance Conductors” every 12 ft.
D: “Service Conductors” every 8 ft.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.