Code Change Summary: A new code section was added to address grounding and bonding terminals used for pool and spa installations.
Pay close attention here. This code change requires a careful read.
A new code section was added to require grounding and bonding terminals related to the pool installation to be identified for use in wet and corrosive environments.
The public input behind the code change was substantiated by the following statement: “Grounding and bonding terminals at pools, spas, hot tubs, etc. are subjected to severe environmental conditions including wet and corrosive conditions. This proposed new text will add specific requirements to address those conditions”.
The new code language states that “field-installed grounding and bonding connections in a damp, wet, or corrosive environment shall be composed of copper, copper alloy, or stainless steel. They shall be listed for direct burial use”.
Throughout Article 680, a precedence has been established that typically allows brass to be used when something metal is required to be corrosion resistant. This new code section does not mention brass but it does mention copper alloy. Here are a few facts that may provide additional insight:
Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2017 NEC® edition of NFPA 70.
2017 Code Language:
N 680.7 Grounding and Bonding Terminals. Grounding and bonding terminals shall be identified for use in wet and corrosive environments. Field-installed grounding and bonding connections in a damp, wet, or corrosive environment shall be composed of copper, copper alloy, or stainless steel. They shall be listed for direct burial use.
Which of the following bonding terminals is permitted for use with pool equipment?
| Please register or sign in for electrical continuing education courses. If you were already signed in, your session probably expired, please sign back in. |