390 Underfloor Raceways.

Underfloor raceways include raceways and associated components designed and intended for installation beneath or flush with the surface of a floor for the installation of cables and electrical conductors.
Click to Enlarge
Underfloor raceways include raceways and associated components designed and intended for installation beneath or flush with the surface of a floor for the installation of cables and electrical conductors.

MA amendments.

390.23. Revise this section to read as follows:

390.23 Ampacity of Conductors. The ampacity adjustment factors in 310.15(C)(1) shall not apply where 30 or fewer current-carrying conductors occupy no more than 20 percent of the interior cross-sectional area of underfloor raceways.

Click here to see the Massachusetts amendments to the 2026 NEC®.

 

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

390 Underfloor Raceways.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is true regarding Underfloor Raceways installed in Massachusetts?

A: The ampacity adjustment factors in 310.15(C)(1) apply when more than 30 current-carrying conductors occupy more than 20 percent of the interior cross-sectional area of underfloor raceways.
B: The ampacity adjustment factors in 310.15(C)(1) never apply.
C: The ampacity adjustment factors in 310.15(C)(1) shall apply to all conductors installed in underfloor raceways.
D: The ampacity adjustment factors in 310.15(A) shall apply to all conductors installed in underfloor raceways.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.