374.23 Cellular metal Floor Raceways.

A cellular metal floor raceway is the hollow spaces of cellular metal floors, together with suitable fittings, that may be approved as enclosed channel for electrical conductors.
Click to Enlarge
A cellular metal floor raceway is the hollow spaces of cellular metal floors, together with suitable fittings, that may be approved as enclosed channel for electrical conductors.

MA amendments.

374.23. Revise this section to read as follows:

374.23 Ampacity of Conductors. The ampacity adjustment factors in 310.15(C)(1) shall not apply where 30 or fewer current-carrying conductors occupy no more than 20 percent of the interior cross-sectional area of cellular metal floor raceways.

Click here to see the Massachusetts amendments to the 2026 NEC®.

 

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

374.23 Cellular metal Floor Raceways.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is true regarding Cellular Metal Floor Raceways installed in Massachusetts?

A: The ampacity adjustment factors in 310.15(C)(1) apply when more than 30 current-carrying conductors occupy more than 20 percent of the interior cross-sectional area of cellular metal floor raceways.
B: The ampacity adjustment factors in 310.15(C)(1) never apply.
C: The ampacity adjustment factors in 310.15(C)(1) shall apply to all conductors installed in cellular metal floor raceways.
D: The ampacity adjustment factors in 310.15(A) shall apply to all conductors installed in cellular metal floor raceways.