Amend NEC® 2017, page 139:
300.9 Raceways in Wet Locations Above grade. Where raceways are installed in wet locations above grade, the interior of these raceways shall be considered to be a wet location. Insulated conductors and cables installed in raceway in wet locations above grade shall comply with 310.10(C).
Exception: The raceway shall not be considered a wet location if:
(1) The section of raceway routed in a wet location above grade does not exceed 1.8 m (6 ft) in length;
(2) Any fittings or conduit bodies are watertight and listed for use in wet locations; and
(3) All termination points of the raceway are only open in any of the following:
ELR commentary: This North Carolina amendment could be used to allow a group of dry location cables to enter the top of a surface mounted panelboard cabinet installed in a wet location outside in accordance with NEC® 312.5(C) exception.
Which of the following is one of the requirements in the NC amendment to NEC 300.9 exception?