OESC 702.4 Capacity and Rating.

For one- and two-family dwellings in Oregon, manual management of the connected load is permitted.
Click to Enlarge

For one- and two-family dwellings in Oregon, manual management of the connected load is permitted.

When it comes to optional standby systems, the NEC® is clear that if using an automatic transfer switch, the standby system must be either capable of supplying the full load or there must be a load management system for the standby system.

This language has been amended in Oregon and now reads as follows:

702.4(A) System Capacity.

(1) Manual and Nonautomatic Load Connection. If the connection of load is manual or nonautomatic, an optional standby system shall have adequate capacity and rating for the supply of all equipment intended to be operated at one time. The user of the optional standby system shall be permitted to select the load connected to the system.

(2) Automatic Load Connection. If the connection of load is automatic, an optional standby system shall comply with 702.4(A)(2)(a) or 702.4(A)(2)(b) in accordance with Article 120 Parts I through IV or by another approved method.

(a) Full Load. The standby source shall be capable of supplying the full load that is automatically connected.

(b) Energy Management System (EMS).

The standby source capacity using an EMS shall automatically manage the connected load and comply with one of the following:

(1) A system employed in accordance with 130.30

(2) A system with a PCS Control setting in accordance with 130.70

Exception: In one- and two-family dwellings manual management of the connected load shall be permitted.

Oregon amendments to the 2026 NEC® are located in “Table 1-E” of the Oregon Electrical Specialty Code (OESC) which can be seen using the following link or the OESC PDF file located near the bottom of the screen: https://www.oregon.gov/bcd/codes-stand/Documents/26oesc-table1-E.pdf

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

OESC 702.4 Capacity and Rating.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is true for an optional standby generator for a single family dwelling?

A: Management of the connected load shall be performed only by load shedding equipment.
B: Manual management of the connected load shall be permitted.
C: The standby generator shall be capable of supplying the full load of the entire dwelling during peak demand.
D: Overcurrent devices for the system shall be selectively coordinated for .01 seconds and greater.