OESC 620.51 Disconnecting Means.

When provided, the disconnecting means shall be located in the elevator control room or control space. The installation shall comply with the requirements of NFPA 72 as adopted in OAR 918-306-0005.
Click to Enlarge
When provided, the disconnecting means shall be located in the elevator control room or control space. The installation shall comply with the requirements of NFPA 72 as adopted in OAR 918-306-0005.

NEC 620.51 provides rules related to the disconnecting means for elevator equipment.

In the OESC, this section was amended as follows:

620.51 Disconnecting Means.

(B) Operation. No provision shall be made to open or close this disconnecting means from any other part of the premises. If sprinklers are installed in hoistways, machine rooms, control rooms, machinery spaces, or control spaces, the disconnecting means shall be permitted to automatically open the power supply to the affected elevator(s) prior to the application of water. No provision shall be made to automatically close this disconnecting means. Power shall only be restored by manual means.

Where provided, this disconnecting means shall be located in the elevator control room or control space. The installation shall comply with the requirements of NFPA 72 as adopted in OAR 918-306-0005.

(C) Location. The disconnecting means shall be located where it is readily accessible to qualified persons.

Where provided, the disconnecting means shall be located in the elevator control room or control space.

Where machine rooms are provided, the disconnecting means required by 620.51 shall be located within 610 mm (24 inches) of the open side of the machine room access door. Where more than one disconnect is required for a multi-car group, the disconnects shall be adjacent to each other with the first disconnect located within 610 mm (24 inches) of the open side of the machine room access door. Measurement shall be taken from the edge of the disconnect nearest the machine room door.

(C)(4) On Platform Lifts and Stairway Chairlifts. On platform lifts and stairway chairlifts, the disconnecting means shall be located within sight of the motor controller or lift and within 1.83 m (six feet) of the motor controller. The disconnecting means shall not be located in the runway enclosure.

(C)(5) Residential installations. A disconnecting means shall be required to be placed within sight of the controller or lift. Where such devices are supplied with flexible cord and plug type connectors, the supply receptacle shall be switched by the disconnecting means. The disconnecting means does not require overcurrent protection, provided such protection is supplied by the branch circuit overcurrent device. In all other respects the disconnecting means shall comply with the requirements of this section.

Oregon amendments to the 2026 NEC® are located in “Table 1-E” of the Oregon Electrical Specialty Code (OESC) which can be seen using the following link or the OESC PDF file located near the bottom of the screen: https://www.oregon.gov/bcd/codes-stand/Documents/26oesc-table1-E.pdfrr

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

OESC 620.51 Disconnecting Means.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

In Oregon, where must the elevator disconnecting means be located if it is installed within a machine room to serve a single elevator car?

A: Within 60 inches of the open side of the machine room access door.
B: Within 48 inches of the open side of the machine room access door.
C: Within 36 inches of the open side of the machine room access door.
D: Within 24 inches of the open side of the machine room access door.
Please register or sign in for electrical continuing education courses.