Oregon has amended the special rules on GFCI protection in Article 547 for specific receptacles.
NEC Article 547 applies to agricultural buildings or that part of a building or adjacent areas of similar nature.
Agricultural areas often include locations inside of a barn or building where excessive dust and dust with water may accumulate. Oregon has amended the special rules on GFCI protection located in Article 547 as follows:
547.28 Receptacles. Ground-fault circuit-interrupter protection shall be provided as required in 210.8(B). GFCI protection shall not be required for other than 125-volt, 15- and 20-ampere receptacles installed within the following areas:
(1) Areas having an equipotential plane
(2) Outdoors
(3) Damp or wet locations
(4) Dirt confinement areas for livestock
GFCI protection shall not be required for a single receptacle supplying a dedicated load and marked “not GFCI protected”. A GFCI protected receptacle shall be located within 900 mm (3 ft) of the non-GFCI protected receptacle.
Oregon amendments to the 2026 NEC® are located in “Table 1-E” of the Oregon Electrical Specialty Code (OESC) which can be seen using the following link or the OESC PDF file located near the bottom of the screen: https://www.oregon.gov/bcd/codes-stand/Documents/26oesc-table1-E.pdf