Replacement receptacles in Oregon have special allowances when it comes to AFCI requirements.
NEC Section 406.12(D) provides rules to follow when replacing existing receptacles. The NEC® states the following:
406.12(D)(4) Arc-Fault Circuit-Interrupter Protection.
If a receptacle supplied by a 120-volt, single-phase, 15- or 20-ampere branch circuit located in any areas specified in 210.12(B), 210.12(C), or 210.12(D) is replaced, a replacement receptacle at this outlet shall be one of the following:
(1) A listed outlet branch-circuit type AFCI receptacle
(2) A receptacle protected by a listed outlet branch-circuit type AFCI type receptacle
(3) A receptacle protected by a listed combination type AFCI circuit breaker
Oregon has amended the above code language and deleted the requirements. Below is the Oregon version of NEC® 406.12(D)(4):
406.12(D)(4) Arc-Fault Circuit Interrupter Protection. (Not adopted by the State of Oregon)
Oregon amendments to the 2026 NEC® are located in “Table 1-E” of the Oregon Electrical Specialty Code (OESC) which can be seen using the following link or the OESC PDF file located near the bottom of the screen: https://www.oregon.gov/bcd/codes-stand/Documents/26oesc-table1-E.pdf
In Oregon, which of the following is true regarding receptacle replacements in an older home where AFCI protection was not originally code required?