NEC Section 334.12 provides a list of things that cannot be done with Nonmetallic Sheathed cable. Oregon has amended this section to add the underlined exception under line item 2:
Uses Not Permitted. Types NM, NMC, and NMS cables shall not be permitted as follows:
[Items (1) and (3) through (12) remain unchanged]
(1) In any dwelling or structure not specifically permitted in 334.10(1), 334.10(2), 334.10(3), and 334.10(5)
(2) Exposed within a dropped or suspended ceiling cavity in other than one- and two-family and multifamily dwellings
Exception to (2): Types NM and NMC cables may be installed within a dropped or suspended ceiling cavity in structures other than one- and two-family and multifamily dwellings when installed in accordance with 334.15.
(3) As service-entrance cable
(4) In commercial garages having hazardous (classified) locations as defined in 511.5
(5) In theaters and similar locations, except where permitted in 518.6(C)
(6) In motion picture studios
(7) In storage battery rooms
(8) In hoistways or on elevators or escalators
(9) Embedded in poured cement, concrete, or aggregate
(10) In hazardous (classified) locations, except where specifically permitted by other articles in this Code.
(11) Direct-buried in the earth
(12) Where subject to physical damage
Oregon amendments to the 2026 NEC® are located in “Table 1-E” of the Oregon Electrical Specialty Code (OESC) which can be seen using the following link or the OESC PDF file located near the bottom of the screen: https://www.oregon.gov/bcd/codes-stand/Documents/26oesc-table1-E.pdf
In Oregon, which of the following is true of nonmetallic sheathed cable (type NM)?
| Please register or sign in for electrical continuing education courses. If you were already signed in, your session probably expired, please sign back in. |