Extensions of a branch circuit are not the same as replacing damaged wiring.
Oregon has heavily amended the code language below regarding AFCI protection:
OESC 210.12(E) Branch Circuit Wiring Extensions, Modifications or Replacements. If branch-circuit wiring for any of the areas specified in 210.12(B), 210.12(C), or 210.12(D) is modified, replaced, or extended, the branch circuit shall be protected by one of the following:
1. By any of the means described in 210.12(A)
2. A listed outlet branch-circuit type AFCI located at the first receptacle outlet of the existing branch circuit.
Exception: AFCI protection shall not be required where the extension of the existing branch-circuit conductors is not more than 1.8 m (6 ft) and does not include any additional outlets or devices, other than splicing devices. This measurement shall not include the conductors inside an enclosure, cabinet, or junction box.
Exception No. 1: Extensions or modifications of existing circuits shall not require the installation of AFCI protection.
Exception No. 2: When a panelboard is upgraded or replaced, AFCI protection shall not be required on existing circuits that were not AFCI protected prior to upgrading or replacing the panelboard.
Oregon amendments to the 2026 NEC® are located in “Table 1-E” of the Oregon Electrical Specialty Code (OESC) which can be seen using the following link or the OESC PDF file located near the bottom of the screen: https://www.oregon.gov/bcd/codes-stand/Documents/26oesc-table1-E.pdf
Which of the following is true of a 120-volt branch circuit in an older dormitory that was not originally required by code to have AFCI protection at the time of installation?