OESC 210.8(A) Exceptions to GFCI Protection.

In Oregon, the rules regarding GFCI protection may be different depending on if the receptacle is a single type or a duplex type and how many appliances it serves.
Click to Enlarge

In Oregon, the rules regarding GFCI protection may be different depending on if the receptacle is a single type or a duplex type and how many appliances it serves.

Oregon has heavily amended the code language below regarding GFCI protection:

210.8(A) Dwelling Units. All 125-volt, single-phase, through 250-volt 15- and 20-ampere receptacles installed in the following locations and supplied by single-phase branch circuits rated 150 volts or less to ground shall have ground-fault circuit-interrupter protection for personnel.

[Items (1) through (5) and (9) through (14) remain unchanged]

(6) Unfinished portions or areas of basements not intended as habitable rooms Basements

(7) Kitchens — where the receptacles are installed to serve the countertop surfaces

(8) Areas with sinks and permanent provisions for food preparation, beverage preparation, or cooking Not adopted by the State of Oregon

[Exceptions No. 1, 3, and 4 remain unchanged]

Exception No. 2: GFCI protection shall not be required for a receptacle supplying only a permanently installed premises security system where the receptacle is labeled as “not GFCI protected.”

Exception No. 5: For the locations in 210.8(A)(2), 210.8(A)(3), 210.8(A)(6), 210.8(A)(7), 210.8(A)(9), and 210.8(A)(12), GFCI protection shall not be required for a single receptacle serving an appliance or a duplex receptacle serving two appliances if all of the following conditions are met:

a. The appliance is located within a dedicated space.

b. In normal use the appliance is not easily moved or is fastened in place.

c. The receptacle is labeled as “not GFCI protected.”

Receptacle(s) installed under this exception shall not be considered as meeting the requirements of 210.52(C) and 210.52(G).

Exception No. 6: For the locations in 210.8(A)(5), GFCI protection shall not be required for a single receptacle supplying a dedicated load and marked “Not GFCI protected,” where a Class A GFCI receptacle is installed within 900 mm (3 ft) of the non-GFCI protected receptacle.

Oregon amendments to the 2026 NEC® are located in “Table 1-E” of the Oregon Electrical Specialty Code (OESC) which can be seen using the following link or the OESC PDF file located near the bottom of the screen: https://www.oregon.gov/bcd/codes-stand/Documents/26oesc-table1-E.pdf

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

OESC 210.8(A) Exceptions to GFCI Protection.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Using 210.8(A) exception 5, which of the following is true of a single-phase, 125-volt, 20-amp, duplex receptacle installed in a dwelling unit laundry room to serve only the clothes washer?

A: It requires GFCI protection.
B: It requires GFP protection.
C: It does not require GFCI protection.
D: It must be a twist-lock type receptacle.