424.47 Label Provided by Manufacturer.

Labels to identify the branch circuit serving space heating cables must be supplied by the manufacturer of the space heating cables.
Click to Enlarge
Labels to identify the branch circuit serving space heating cables must be supplied by the manufacturer of the space heating cables.

Code Change Summary: A new code section was added to address identification of circuits feeding space heating cables.

A new requirement was added in the 2017 NEC® which is really directed at manufacturers of space heating cables. The new rule requires the manufacturer of electric space heating cables to provide marking labels that indicate that the overall space-heating installation incorporates electric space-heating cables. As well, the manufacturer is also required to mention (in the installation instructions) that the labels must be affixed to the panelboards in order to identify which branch circuits supply the space-heating installations.

If the electric space-heating cables happen to still be visible after installation, the labels are not required to be affixed to the panelboards.

The intent of the code requirement is to make sure those who may be about to drill through or anchor something to the floor, wall or ceiling are made aware of the cables located just under the surface.

Similar requirements were previously located in 424.92(D) and only applied to heating panels or heating panel sets but made no mention of heating cables which seem to be more common.

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2017 NEC® edition of NFPA 70.

2017 Code Language:

N 424.47 Label Provided by Manufacturer. The manufacturers of electric space-heating cables shall provide marking labels that indicate that the space-heating installation incorporates electric space-heating cables and instructions that the labels shall be affixed to the panelboards to identify which branch circuits supply the circuits to those space-heating installations. If the electric space-heating cable installations are visible and distinguishable after installation, the labels shall not be required to be provided and affixed to the panelboards.

Did You Like This? Let Us Know With A Like! Thanks!

424.47 Label Provided by Manufacturer.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is required for a space heating cable installation?

A: The electrician must create labels that identify the presence of heating cables.
B: The manufacturer of electric space-heating cables must install marking labels at the electric panel.
C: The manufacturer’s instructions must state that the labels shall be affixed to the panelboards to identify which branch circuits supply the circuits to those space-heating installations.
D: Branch circuits serving fixed electric space heating must be of the GFCI type.