WAC 296-46B-450 Equipment for general use — Transformers and transformer vaults including secondary ties.

Click to Enlarge

WAC 296-46B-450 Equipment for general use — Transformers and transformer vaults including secondary ties.

027 Flammable-liquid or oil-filled transformers installed outdoors.

(1) Flammable-liquid or oil-filled transformers installed outdoors must meet the following requirements:

(a) A transformer installed adjacent to a building/structure with any combustible surface may be located only in the shaded "Approved Transformer Area" shown in Figure 450-1;

(b) A transformer installed adjacent to a building/structure with no combustible surface(s) may be located only in the shaded "Approved Transformer Area" shown in Figure 450-2;

(c) In an area in which a transformer is to be installed next to a nonhabitable structure, the transformer may be no closer than two feet to the building/structure and must be outside a line extended vertically from the ends of the eaves or rooflines;

(d) A building/structure may have no doors, windows, stairways, or other openings closer than eight feet to the transformer;

(e) The finished grade at the location of the transformer must be such that any oil leaking from the transformer will flow away from the building/structure and will not pool; and

(f) If transformers are installed in areas subject to traffic other than pedestrian traffic, they must be provided with adequate guarding.

(2) Enclosures for total underground flammable-liquid or oil-filled transformers must not be located within eight feet of a doorway, operable window, stairways or fire escape. Adequate space must be maintained above the enclosure so that a boom may be used to lift the transformer from the enclosure.

  Click here to review the Washington Administrative Code  

Did You Like This? Let Us Know With A Like! Thanks!

WAC 296-46B-450 Equipment for general use — Transformers and transformer vaults including secondary ties.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

In Washington, which of the following is true regarding oil-filled transformers installed outside?

A: A transformer installed adjacent to a building with noncombustible surfaces must be located not closer than 8 feet from the building.
B: A transformer installed adjacent to a building with combustible surfaces must be located not closer than 2 feet from the building.
C: A transformer installed adjacent to a building with noncombustible surfaces must be located not closer than 2 feet from the building.
D: There must be no doors closer than 2 feet from the transformer.