WAC 296-46B-450 Equipment for general use — Transformers and transformer vaults including secondary ties.

Click to Enlarge

WAC 296-46B-450 Equipment for general use — Transformers and transformer vaults including secondary ties.

027 Flammable-liquid or oil-filled transformers installed outdoors.

(1) Flammable-liquid or oil-filled transformers installed outdoors must meet the following requirements:

(a) A transformer installed adjacent to a building/structure with any combustible surface may be located only in the shaded "Approved Transformer Area" shown in Figure 450-1;

(b) A transformer installed adjacent to a building/structure with no combustible surface(s) may be located only in the shaded "Approved Transformer Area" shown in Figure 450-2;

(c) In an area in which a transformer is to be installed next to a nonhabitable structure, the transformer may be no closer than two feet to the building/structure and must be outside a line extended vertically from the ends of the eaves or rooflines;

(d) A building/structure may have no doors, windows, stairways, or other openings closer than eight feet to the transformer;

(e) The finished grade at the location of the transformer must be such that any oil leaking from the transformer will flow away from the building/structure and will not pool; and

(f) If transformers are installed in areas subject to traffic other than pedestrian traffic, they must be provided with adequate guarding.

(2) Enclosures for total underground flammable-liquid or oil-filled transformers must not be located within eight feet of a doorway, operable window, stairways or fire escape. Adequate space must be maintained above the enclosure so that a boom may be used to lift the transformer from the enclosure.

  Click here to review the Washington Administrative Code  

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

WAC 296-46B-450 Equipment for general use — Transformers and transformer vaults including secondary ties.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

In Washington, which of the following is true regarding oil-filled transformers installed outside?

A: A transformer installed adjacent to a building with noncombustible surfaces must be located not closer than 8 feet from the building.
B: A transformer installed adjacent to a building with combustible surfaces must be located not closer than 2 feet from the building.
C: A transformer installed adjacent to a building with noncombustible surfaces must be located not closer than 2 feet from the building.
D: There must be no doors closer than 2 feet from the transformer.