WAC 296-46B-210 Branch circuits not over 1,000 volts ac, 1,500 volts dc nominal.

Click to Enlarge

WAC 296-46B-210 Wiring and protection — Branch circuits.

008(B) Other than dwelling units - GFCI requirements.

(3) GFCI requirements. GFCI protection for personnel will not be required for:

(a) Three-phase receptacles unless specifically required elsewhere in the NEC; or

(b) Receptacles other than 125-volt, single phase, 15- or 20-am-pere used for: Recreational vehicle supply equipment or for attachment of a mobile home supply cord.

For the purposes of NEC® 210.8(B), kitchen means any area where utensils, dishes, etc., are cleaned or where food or beverages are prepared or cooked.

011 Branch circuits.

(4) A raceway system or one dedicated 15 – ampere minimum, 120 volt circuit must be taken to all unfinished space areas adaptable to future dwelling unit living areas that are not readily accessible to the service or branch circuit panelboard. One circuit or raceway is required for each 480 square feet or less of unfinished space area. If the total adjacent unfinished space area is less than 480 square feet, the circuit can be an extension of an existing circuit. The circuits must terminate in a suitable box(es). The box must contain an identification of the intended purpose of the circuit(s). The branch circuit panelboard must have adequate space and capacity for the intended load(s).

013 Ground fault protection of equipment.

(5) Equipment ground fault protection systems required by the NEC® must be tested prior to being placed into service to verify proper installation and operation of the system as determined by the manufacturer’s published instructions. A firm having qualified personnel and proper equipment must perform the tests required. A copy of the manufacturer’s performance testing instructions and a written performance acceptance test record signed by the person performing the test must be available at the time of inspection. The performance acceptance test record must include test details including, but not limited to, all trip settings and measurements taken during the test.

  Click here to review the Washington Administrative Code  

Did You Like This? Let Us Know With A Like! Thanks!

WAC 296-46B-210 Branch circuits not over 1,000 volts ac, 1,500 volts dc nominal.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

In Washington, which of the following is true regarding GFCI protection for receptacles?

A: GFCI protection is required for all receptacles rated 15 amps or larger.
B: GFCI protection is required for all three phase receptacles regardless of amperage rating.
C: GFCI protection for personnel will not be required for three-phase receptacles unless specifically required elsewhere in the NEC.
D: GFCI protection is only required for three phase receptacles in a commercial kitchen.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.