215.2(A)(1) Feeders. Minimum Rating and Size.

Conductor ampacity table 310.15(B)(16) and Table 310.15(B)(2)(a) for ambient temperature correction factors.
Click to Enlarge
Conductor ampacity table 310.15(B)(16) and Table 310.15(B)(2)(a) for ambient temperature correction factors.

Code Change Summary: New code language was added to clarify how a feeder is sized.

The code language added to this section in the 2014 NEC® is not a new concept. It is just a clarification. Feeder conductors are still calculated the same way as before but the revised code language is a bit more user friendly.

Now, it is clear than when sizing a feeder, the larger of two values is used for the final selection of the conductor:

OR

Before this code change, some electrician were taking 125% of the continuous load and then applying additional adjustment or correction factors which results in an oversized feeder conductor. See the example below for the 3-step method to properly size a feeder:

Example: What minimum size copper type THW feeder conductors are required to supply a 60-amp continuous load where the feeders are installed in an area where the ambient temperature is 125°F? (Assume all terminations are rated 75°C for simplicity)

Step 1, take 60 amps X 125% which = 75 amps. Select a THW copper conductor from Table 310.15(B)(16) that can carry 75 amps from the 75° column (#4 AWG).

Step 2, take 60 amps ÷ .67 (based on 125°F ambient temperature and Table 310.15(B)(2)(a)).

60 ÷ .67 = 90 amps. Select a THW copper conductor from Table 310.15(B)(16) that can carry 90 amps from the 75° column (#3 AWG).

Step 3, compare results from the first two steps and pick the larger wire which is 3 AWG copper.

Below is a preview of the NEC®.  See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on the “free access” tab and select the applicable year of NFPA 70 (National Electrical code).

2011 Code Language:

215.2(A)(1) General. Feeder conductors shall have an ampacity not less than required to supply the load as calculated in Parts III, IV, and V of Article 220. The minimum feeder-circuit conductor size, before the application of any adjustment or correction factors, shall have an allowable ampacity not less than the noncontinuous load plus 125 percent of the continuous load.

2014 Code Language:

215.2(A)(1) General. Feeder conductors shall have an ampacity not less than required to supply the load as calculated in Parts III, IV, and V of Article 220. Conductors shall be sized to carry not less than the larger of 215.2(A)(1)(a) or (b).

(a) Where a feeder supplies continuous loads or any combination of continuous and noncontinuous loads, the minimum feeder conductor size shall have an allowable ampacity not less than the noncontinuous load plus 125 percent of the continuous load.

(b) The minimum feeder conductor size shall have an allowable ampacity not less than the maximum load to be served after the application of any adjustment or correction factors.

Did You Like This? Let Us Know With A Like! Thanks!

215.2(A)(1) Feeders. Minimum Rating and Size.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

What minimum size copper type THW feeder conductors are required to supply a 40-amp continuous load where the feeders are installed in an area where the ambient temperature is 125°F? (Assume all terminations are rated 75°C for simplicity)

A: 8 AWG.
B: 6 AWG.
C: 4 AWG.
D: 3 AWG.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.