409.22 Short-Circuit Current Rating.

Having the calculation for the available short-circuit current ensures that the inspector can double check to see that the proper length, size and type of conductors were used to come up with the final value.
Click to Enlarge
Having the calculation for the available short-circuit current ensures that the inspector can double check to see that the proper length, size and type of conductors were used to come up with the final value.

Code Change Summary: Changes were made regarding the short-circuit current marking of industrial control panels.

An “industrial control panel” can be factory made and very elaborate or something as simple as two lighting contactors, field installed in a large junction box. Article 100 defines an Industrial Control Panel as an assembly of two or more components consisting of one of the following:

(1) power circuit components only, such as motor controllers, overload relays, fused disconnect switches, and circuit breakers;

(2) control circuit components only, such as push buttons, pilot lights, selector switches, timers, switches, and control relays;

(3) a combination of power and control circuit components. These components, with associated wiring and terminals, are mounted on, or contained within, an enclosure or mounted on a subpanel.

In the 2014 NEC®, Section 409.22 required industrial control panels to be installed at a point along the circuit where the available fault current doesn’t exceed the short-circuit current rating (SCCR) of the industrial control panel.

In the 2017 NEC® the language was clarified and expanded. Now, an industrial control panel shall not be installed where the available “short-circuit current” exceeds its short-circuit current rating. As well, a calculation must be performed to determine how much short-circuit current is available at the control panel. The amount of short-circuit current refers to the amount of current that could be delivered to the industrial control panel under a short-circuit condition that may occur in the control panel.

These rules help to bring everything in compliance with NEC® 110.10. Knowing the amount of short-circuit current available at the industrial control panel is the first step in selecting the right control panel. For example, if a calculation is performed and it is found that the amount of short-circuit current available at a control panel is 4,999 amps, then installing an industrial control panel with a short-circuit current rating of 5,000 amps is code compliant.

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2017 NEC® edition of NFPA 70.

2014 Code Language:

409.22 Short-Circuit Current Rating. An industrial control panel shall not be installed where the available fault current exceeds its short-circuit current rating as marked in accordance with 409.110(4).

2017 Code Language:

409.22 Short-Circuit Current Rating.

(A) Installation. An industrial control panel shall not be installed where the available short-circuit current exceeds its short-circuit current rating as marked in accordance with 409.110(4).

(B) Documentation. If an industrial control panel is required to be marked with a short-circuit current rating in accordance with 409.110(4), the available short-circuit current at the industrial control panel and the date the short-circuit current calculation was performed shall be documented and made available to those authorized to inspect the installation.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

409.22 Short-Circuit Current Rating.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is true for an industrial control panel that is required to be marked with a short-circuit current rating?

A: The available short-circuit current at the industrial control panel and the date the short-circuit current calculation was performed shall be documented and made available to those authorized to inspect the installation.
B: It shall not be installed where the available fault current is less than its interrupt rating.
C: It must be installed where the available fault current exceeds its short-circuit current rating.
D: It must also be marked with an available fault current rating.