2022-2023 License and Installation Concerns Bulletin.
The Electricians' Licensing Board in conjunction with the State Electrical Inspectors, municipal electrical & building inspectors & other representatives of the electrical industry in the State of New Hampshire have put together this list of common licensing and installation concerns and problems encountered by the Board's office staff relative to the State's licensing law RSA 319-C and the administrative rules.
11. Prime mover shutdown for permanently installed generators
Generators with greater than 15 kW rating shall be provided with a remote emergency stop switch to shut down the prime mover. The remote emergency stop switch shall be located outside the equipment room or generator enclosure and shall also meet the requirements of 445.18(B)(1) and (B)(2).
A new requirement in the 2020 Code requires an emergency shutdown outside for a generator installed at a one- or two-family dwelling unit.
Which of the following is required for the prime mover shutdown for permanently installed generators?