The grounding electrode system requirements for a PV system seem to change with each new code cycle. As well, certain rules back in Article 250 may permit the grounding electrode conductor for the PV system to be as small as 14 AWG copper.
In Oregon, the minimum size of the grounding electrode conductor for a PV system is simple. See the amended OESC code language below:
690.47 Grounding Electrodes and Grounding Electrode Conductors.
Additional grounding electrodes shall be permitted to be installed in accordance with 250.52 and 250.54. Grounding shall be permitted to be connected directly to the PV module frame(s) or support structure. A grounding electrode conductor shall be sized according to 250.66, and shall not be smaller than 6 AWG copper or 4 AWG aluminum.
Oregon amendments to the 2020 NEC® are located in “Table 1-E” of the Oregon Electrical Specialty Code (OESC) which can be seen using the following link or the OESC PDF file located near the bottom of the screen: https://www.oregon.gov/bcd/codes-stand/Documents/21oesc-table1-e-2021April.pdf
Which of the following is required when installing a grounding electrode system for a photovoltaic system installation?