NEC 620.37 covers wiring in hoistways, machine rooms, control rooms, machinery spaces, and control spaces related to the elevator.
In the OESC, this section was amended to address conduits and raceways related to such areas as follows:
620.37 Wiring in Hoistways, Machine Rooms, Control Rooms, Machinery Spaces, and Control Spaces.
(A) Uses Permitted. Only such electrical wiring, raceways, and cables used directly in connection with the elevator or dumbwaiter, including wiring for signals, for communication with the car, for lighting, heating, air conditioning, and ventilating the elevator car, for fire detecting systems, for pit sump pumps, and for heating, lighting, and ventilating the hoistway, shall be permitted inside the hoistway, machine rooms, control rooms, machinery spaces, and control spaces.
Conduits and raceways necessary for the connection of such devices shall only enter hoistways and machine rooms to the extent necessary to connect the devices(s) attached thereto.
Oregon amendments to the 2020 NEC® are located in “Table 1-E” of the Oregon Electrical Specialty Code (OESC) which can be seen using the following link or the OESC PDF file located near the bottom of the screen: https://www.oregon.gov/bcd/codes-stand/Documents/21oesc-table1-e-2021April.pdf
According to the OESC, which of the following is true regarding conduits or raceways entering an elevator machine room?