314.28(E)(1) Power Distribution Blocks. Installation.

Whether in a wireway or any other box, power distribution blocks installed on the line side of the service equipment shall be listed and marked “suitable for use on the line side of service equipment” or equivalent.
Click to Enlarge
Whether in a wireway or any other box, power distribution blocks installed on the line side of the service equipment shall be listed and marked “suitable for use on the line side of service equipment” or equivalent.

Code Change Summary: New requirements were added about the listing of power distribution blocks.

Power distribution blocks are most commonly used in metal wireways (covered in Article 376) but there is nothing prohibiting their use in other enclosures.

In the 2014 NEC®, code language was added in 376.56(B)(1) to ensure that power distribution blocks installed on the line side of the service equipment are listed for the purpose. Before the code language was added, it was common practice to see any kind of power distribution block used ahead of a service disconnect with no regard to the suitability of the product being located on the line side of any overcurrent protection.

By locating the above code language only in Article 376, it would only be applicable if the power distribution blocks were installed in a metal wireway.

In the 2017 NEC®, similar code language was added to 314.28(E)(1). Now that the requirement is also repeated in Article 314, it will apply to power distribution blocks in any box or enclosure.

Below is a preview of Article 314. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2017 NEC® edition of NFPA 70.

2014 Code Language:

314.28(E)(1) Installation. Power distribution blocks installed in boxes shall be listed.

2017 Code Language:

314.28(E)(1) Installation. Power distribution blocks installed in boxes shall be listed. Power distribution blocks installed on the line side of the service equipment shall be listed and marked “suitable for use on the line side of service equipment” or equivalent.

Did You Like This? Let Us Know With A Like! Thanks!

314.28(E)(1) Power Distribution Blocks. Installation.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is true when installing power distribution blocks?

A: All power distribution blocks are listed as suitable for use on the line side of service equipment.
B: Only power distribution blocks in a metal wireway on the line side of service equipment must be listed as suitable for use on the line side of service equipment.
C: Power distribution blocks are only permitted to be installed on the line side of service equipment.
D: Power distribution blocks ahead of service equipment must be listed and marked to indicate that they are suitable for use on the line side of service equipment.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.