314.27(E) Separable Attachment Fittings

This type of receptacle has two parts. One half connects to the luminaire and mates with a compatible attachment fitting mounted inside the ceiling box.
Click to Enlarge
This type of receptacle has two parts. One half connects to the luminaire and mates with a compatible attachment fitting mounted inside the ceiling box.

Code Change Summary: A new code section was added to address “Separable Attachment Fittings”.

New and innovative products emerging in the electrical industry sometimes warrant the need for a code change. Section 314.27(E) is new in the 2017 NEC® and creates the code language needed to allow a new type of receptacle to be installed inside boxes.

In the 2017 NEC®, the definition of a “receptacle” was revised in Article 100:

Receptacle. A contact device installed at the outlet for the connection of an attachment plug, or for the direct connection of electrical utilization equipment designed to mate with the corresponding contact device.

The new definition aligns with the typical receptacles used in most electrical systems as well as a new product that can be used to make the installation of ceiling fans and luminaires much easier (see image).

Now, Outlet boxes are permitted to support listed locking support and mounting receptacles used in combination with compatible attachment fittings. The combination must be identified for the support of equipment within the weight and orientation limits of the product listing. Where the supporting receptacle is installed within a box, it must be included in the fill calculation mentioned in 314.16(B)(4) which covers device or equipment fill.

The receptacle in the image is designed to be installed inside a box. It allows the installer to wire in one half of the receptacle and attach the other compatible attachment fitting to a luminaire or ceiling fan. The luminaire or fan can then simply be lifted and plugged into place.

See 422.18 for similar code language related to ceiling fans.

Below is a preview of Article 314. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2017 NEC® edition of NFPA 70.

2017 Code Language:

N 314.27(E) Separable Attachment Fittings. Outlet boxes required in 314.27 shall be permitted to support listed locking support and mounting receptacles used in combination with compatible attachment fittings. The combination shall be identified for the support of equipment within the weight and mounting orientation limits of the listing. Where the supporting receptacle is installed within a box, it shall be included in the fill calculation covered in 314.16(B)(4).

Did You Like This? Let Us Know With A Like! Thanks!

314.27(E) Separable Attachment Fittings

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

If installing separable attachment fittings in a box, which of the following is true?

A: Device fill calculations are NOT required for a receptacle in a box.
B: Where the supporting receptacle is installed within a box, it shall be included in the fill calculation covered in 314.16(B)(4).
C: Boxes are NOT permitted to support “listed locking support and mounting receptacles”.
D: Ceiling mounted boxes are NOT permitted to contain receptacles.