Table 300.5 Minimum Cover Requirements.

New footnotes (a & b) are special allowances for listed low-voltage lighting systems.
Click to Enlarge
New footnotes (a & b) are special allowances for listed low-voltage lighting systems.

Code Change Summary: New footnotes appear under Table 300.5.

NEC Table 300.5 provides minimum cover requirements for wiring methods and raceways from zero to 1000 volts. There is a common misconception that spare, unused raceways and low voltage installations are exempt from the requirements in the table. The simple fact that the table covers installations starting at zero volts says otherwise.

It is important to remember that minimum cover and minimum trench depth are not the same. According to note 1 under the table, cover is defined as the shortest distance in inches between a point on the top surface of any direct-buried conductor, cable, conduit, or other raceway and the top surface of finished grade, concrete, or similar cover. In order to get the proper cover over the top of the wiring method, the overall depth of the trench will need to be deeper than the minimum cover requirements.

Column 5 of Table 300.5 provides the cover depth for irrigation and landscape lighting circuits operating at 30 volts or less and installed using UF cable or other identified cables or raceways. Unless covered by concrete or installed directly under a building, the minimum cover depth in column 5 is six inches.

In some cases, the manufacturer furnishes the wiring method for the lighting kit which may include cables that are not intended for direct burial outdoors but may be suitable for indoor installations just under the top soil or bark in an above grade planter box. For these listed lighting systems, the installation instructions will specify if the wiring method can be buried at all and if so, the minimum or maximum required burial depth.

In the 2017 NEC®, two new footnotes were added to specifically address listed low-voltage lighting systems:

Below is a preview of Article 300. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2017 NEC® edition of NFPA 70.

2017 Code Language:

Table 300.5 footnotes:

a A lesser depth shall be permitted where specified in the installation instructions of a listed low voltage lighting system.

b A depth of 150 mm (6 in.) shall be permitted for pool, spa, and fountain lighting, installed in a nonmetallic raceway, limited to not more than 30 volts where part of a listed low-voltage lighting system.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

Table 300.5 Minimum Cover Requirements.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is true when installing a listed, 24 volt, lighting system for a fountain inside a hotel lobby?

A: The wiring method must be buried at least 12 inches deep.
B: The wiring method must be buried at least 18 inches deep.
C: A depth of 6 inches shall be permitted for pool, spa, and fountain lighting, installed in a nonmetallic raceway, limited to not more than 30 volts where part of a listed low-voltage lighting system.
D: The wiring method must be buried at least 24 inches deep.
Please register or sign in for electrical continuing education courses.