230.66 Marking.

One of the many reasons why the inspector red tagged this installation is because the new 200-amp electric service panel was installed under the existing 60-amp rated meter socket. Can you spot any other issues?
Click to Enlarge
One of the many reasons why the inspector red tagged this installation is because the new 200-amp electric service panel was installed under the existing 60-amp rated meter socket. Can you spot any other issues?

Code Change Summary: Additional code language now requires listing of meter socket enclosures.

Meter sockets are now required to be listed and properly rated for the applied voltage and ampacity of the electric service. This should help to reduce the number of older meter installations where an existing electric service is replaced with a larger ampacity service but the old meter socket enclosure is left in place for the utility company to worry about.

Often, the utility company assumes that the presence of the inspector’s green tag on a replacement electric service means the meter socket was inspected also for proper ampacity and ratings. As well, quite often, the inspector arrives and only looks at the equipment installed downstream of the meter socket enclosure. Many inspectors aren’t sure where their responsibility stops and the utility company begins.

In some areas of the country, the electric utility company supplies the meter socket enclosure for the electrical service installation.

By having new code language about it in the NEC®, it now becomes clear that the electrician and the inspector both share responsibility in making sure the meter socket enclosure is listed and rated properly.

Below is a preview of Article 230. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2017 NEC® edition of NFPA 70.

2014 Code Language:

230.66 Marking. Service equipment rated at 1000 volts or less shall be marked to identify it as being suitable for use as service equipment. All service equipment shall be listed. Individual meter socket enclosures shall not be considered service equipment.

2017 Code Language:

230.66 Marking. Service equipment rated at 1000 volts or less shall be marked to identify it as being suitable for use as service equipment. All service equipment shall be listed or field labeled. Individual meter socket enclosures shall not be considered service equipment but shall be listed and rated for the voltage and ampacity of the service.

Exception: Meter sockets supplied by and under the exclusive control of an electric utility shall not be required to be listed.

Did You Like This? Let Us Know With A Like! Thanks!

230.66 Marking.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is true of a meter socket enclosure for an electric service?

A: Meter sockets supplied by and under the exclusive control of an electric utility are not required to be listed.
B: Meter sockets supplied by and under the exclusive control of an electric utility must always be listed.
C: Individual meter socket enclosures are considered service equipment.
D: Meter socket enclosures are covered in NEC Article 314.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.