215.2(A)(1) Feeders Not More Than 600 Volts. General.

Installing 90°C rated power distribution blocks and a gutter at each end of a long run of feeder just before terminating the feeders in the panelboard at each end can create a situation where smaller size 90°C rated wire can be run between gutter boxes.
Click to Enlarge
Installing 90°C rated power distribution blocks and a gutter at each end of a long run of feeder just before terminating the feeders in the panelboard at each end can create a situation where smaller size 90°C rated wire can be run between gutter boxes.

Code Change Summary: The exceptions for feeder sizing were reorganized and a new exception was added.

When sizing an ungrounded feeder conductor, section 215.2(A)(1) allows the larger of the following two values to be used for the final selection of the conductor:

OR

In the 2017 NEC®, this remains unchanged. What has changed is the location of the exceptions. They have been relocated to just behind 215.2(A)(1)(a) to make it clear that they do not apply to 215.2(A)(1)(b) at all.

More importantly, new exception 2 was added. This new exception requires a very careful read in order to understand it. The new exception allows a portion of a feeder connected between pressure connectors (such as power distribution blocks) complying with 110.14(C)(2) to be sized based on the continuous load plus the noncontinuous load rather than 125% of the continuous load plus the noncontinuous load.

The idea is this: Most equipment and circuit breaker terminals are rated at 75°C. Even if a conductor is rated at 90°C, it must be considered as a 75°C conductor if terminating to a 75°C terminal. This means that a 1 AWG copper type XHHW-2 conductor (rated for 145 amps in the 90°C column of Table 310.15(B)(16)) is really only rated for 130 amps (from the 75°C column) if terminating on 75°C rated terminals at each end (see illustration).

Section 110.14(C)(2) covers separately installed pressure connectors such as power distribution blocks and recognizes the fact that many of them differ from circuit breaker terminals in that they are often rated higher than 75°C.

According to the new exception, a run of 90°C rated feeder conductors installed between 90°C rated power distribution blocks can be used at its maximum ampacity based on 90°C.

This principle would allow a pull box to be installed at each end of a feeder just before the conductors enter the overcurrent device enclosure or equipment. If 90°C rated power distribution blocks are used at each end of the feeder inside each pull box, then technically, a smaller, less expensive conductor such as a 2 AWG copper type XHHW-2 (rated for 130 amps in the 90°C column of Table 310.15(B)(16)) can be used at its full value of 130 amps but only for the portion of the feeder between the 90°C rated pressure connectors or power distribution blocks.

From the power distribution blocks down to the termination of the overcurrent device or equipment, a larger conductor would be used after it is sized based on 125% of the continuous load or 100% of the continuous load after applying correction factors based on conditions of use (whichever is larger). This is because it will be directly connected to either the overcurrent device or the equipment where the load is applied. In most cases, these will each have 75°C rated terminals.

The weakest point along a 90°C rated conductor is where it connects to the 75°C rated terminal. The new exception recognizes the fact that the middle of a conductor run between 90°C rated terminals can be sized smaller than the ends which land on a lesser rated terminal.

The last sentence of exception 2 states that if this method is used, the smaller, middle run of feeder is not permitted to extend beyond the pull boxes into the associated equipment (see image).

Below is a preview of Article 215. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2017 NEC® edition of NFPA 70.

2017 Code Language:

215.2(A)(1) General.

Exception No. 2: Where a portion of a feeder is connected at both its supply and load ends to separately installed pressure connections as covered in 110.14(C)(2), it shall be permitted to have an allowable ampacity not less than the sum of the continuous load plus the noncontinuous load. No portion of a feeder installed under the provisions of this exception shall extend into an enclosure containing either the feeder supply or the feeder load terminations, as covered in 110.14(C)(1).

Did You Like This? Follow us on Face Book! Thanks!

Electrical License Renewal Facebook Logo

215.2(A)(1) Feeders Not More Than 600 Volts. General.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is required when using 215.2(A)(1) exception 2?

A: If exception 2 is used, the portion of the feeder connected between 90°C rated power distribution blocks must be rated at least 60°C.
B: Conductors installed under the provisions of exception 2 must extend to the actual terminals of the load.
C: The portion of the feeder installed under the provisions of exception 2 CANNOT extend into an enclosure containing the feeder supply terminations.
D: Conductors installed under the provisions of exception 2 must be rated twice the ampacity of the load.
Please register or sign in for electrical continuing education courses.