110.26(E)(2) Dedicated Equipment Space Outdoors.

Dedicated equipment space outdoors applies to switchboards, switchgear, panelboards, motor control centers. The roof drain above the outdoor panelboard encroaches into the required dedicated equipment space.
Click to Enlarge
Dedicated equipment space outdoors applies to switchboards, switchgear, panelboards, motor control centers. The roof drain above the outdoor panelboard encroaches into the required dedicated equipment space.

Code Change Summary: The dedicated equipment space requirements for certain outdoor equipment has been reworked into a list format and an exception was added.

Switchboards, switchgear, panelboards, and motor control centers have specific dedicated equipment space requirements. Dedicated equipment space is not the same as working space. Dedicated space is a specific area that is devoted to the electrical installation for the purpose of installing raceways, cables and electrical equipment associated with the overall electrical installation. The dedicated equipment space has different rules and allowances based on indoor or outdoor installations.

The new exception needs to be read carefully in order to make an attempt at applying it.

The new exception allows structural overhangs or roof extensions to be permitted “in this zone”. What zone? The “zone” that the exception speaks of is the work space zone.

Notice the exception is located just under 110.26(E)(2)(b) which is all about making sure the equipment requiring the dedicated equipment space complies with the working space rules in 110.26(A). This appears to be a mistake. The original code change proposals (public inputs 1226 and 4628) intended to address structural overhangs above the dedicated equipment space, not the equipment’s workspace. This code change is likely to see a revision in the 2020 NEC®.

Notice that 110.26(E)(2)(c) remains unchanged. This section is about keeping foreign piping and equipment out of the dedicated equipment space. This section is not about architectural or structural overhangs. Electrician are masters at figuring out ways to get a pipe around or through an obstacle or structural overhang into an enclosure.

Below is a preview of Article 110. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2017 NEC® edition of NFPA 70.

2014 Code Language:

110.26(E)(2) Outdoor. Outdoor installations shall comply with 110.26(E)(2)(a) and (b).

(a) Installation Requirements. Outdoor electrical equipment shall be installed in suitable enclosures and shall be protected from accidental contact by unauthorized personnel, or by vehicular traffic, or by accidental spillage or leakage from piping systems. The working clearance space shall include the zone described in 110.26(A). No architectural appurtenance or other equipment shall be located in this zone.

(b) Dedicated Equipment Space. The space equal to the width and depth of the equipment, and extending from grade to a height of 1.8 m (6 ft) above the equipment, shall be dedicated to the electrical installation. No piping or other equipment foreign to the electrical installation shall be located in this zone.

2017 Code Language:

110.26(E)(2) Outdoor. Outdoor installations shall comply with 110.26(E)(2)(a) through (c).

(a) Installation Requirements. Outdoor electrical equipment shall be the following:

(1) Installed in identified enclosures

(2) Protected from accidental contact by unauthorized personnel or by vehicular traffic

(3) Protected from accidental spillage or leakage from piping systems

(b) Work Space. The working clearance space shall include the zone described in 110.26(A). No architectural appurtenance or other equipment shall be located in this zone.

Exception: Structural overhangs or roof extensions shall be permitted in this zone.

(c) Dedicated Equipment Space. The space equal to the width and depth of the equipment, and extending from grade to a height of 1.8 m (6 ft) above the equipment, shall be dedicated to the electrical installation. No piping or other equipment foreign to the electrical installation shall be located in this zone.

Did You Like This? Let Us Know With A Like! Thanks!

110.26(E)(2) Dedicated Equipment Space Outdoors.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

One of the following is NOT true for an outdoor panelboard. Which of the following is NOT true for an outdoor panelboard?

A: They shall be installed in identified enclosures.
B: They shall be protected from accidental contact by vehicular traffic.
C: Roof extensions are permitted in the zone described in 110.26(A).
D: Foreign piping is permitted within the zone extending 6 inches above the panelboard.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.