Table 110.26(A)(1) Working Spaces.

Comparison of Table 110.26(A)(1) in the 2014 NEC and 2017 NEC.
Click to Enlarge
Comparison of Table 110.26(A)(1) in the 2014 NEC and 2017 NEC.

Code Change Summary: The voltage levels and measurements in Table 110.26(A)(1) have changed.

NEC Table 110.26(A)(1) provides the minimum required work space depth for electrical equipment rated 0-1000 volts (to ground) that is likely to be examined or worked on while energized.

For quite some time, this table stopped at 600 volts and the work space depth for anything higher than that was determined from Table 110.31 in Part III of Article 110.

In the 2017 NEC®, new dimensions are given for work space depth when the voltage to ground is between 601 volts and 1000 volts. Conditions 1, 2 and 3 under the table remain unchanged are critical in determining proper working space (see image).

Work space depth is measured from the exposed live parts or from the enclosure or opening if the live parts are enclosed (such as a panelboard inside a cabinet).

See the illustration for a preview of the revised Table 110.26(A)(1). See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2017 NEC® edition of NFPA 70.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

Table 110.26(A)(1) Working Spaces.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Based on conditions under Table 110.26(A)(1), what is the minimum required work space depth for the area in front of a 480 volt panelboard (277 volts to ground) located on one side of the work space and a brick wall on the other side?

A: 3 ft.
B: 3 ft. 6 in.
C: 4 ft.
D: 5 ft.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.