Code Change Summary: New requirements for arc-flash hazard warning labels provide specific rules for service equipment rated 1200 amps or more.
Read carefully here. This is a BIG deal.
New labeling requirements in 110.16 really put the pressure on for electrician to step up their game. Now, in other than dwelling units, service equipment rated 1200 amps or more must be marked with certain items that can only be obtained by an electrician who truly brings their A-game to the job site.
When a 1200 amp or larger electric service is installed at other than dwelling units, the following markings must be field or factory applied to the service equipment:
Item 1 above is no big deal. It is expected that the installing electrician will know the nominal system voltage for the equipment being installed.
Item 2 has basically been required anyway since the 2011 NEC® in section 110.24(A) so this is not a major change. To obtain the available fault current (AFC) at the service, most electrician will contact the local utility company to find out the maximum AFC that can be delivered from the transformer secondary to the service.
Item 3 is the game changer. In order to accurately mark the clearing time of the overcurrent device, the electrician will need to understand the time-current curve charts for the specific overcurrent device being used at the 1200 amp or larger service. Take notice that the NEC® does NOT require an electrical engineer to be involved with this one. When the NEC® requires an electrical engineer to get involved, the NEC® states just that. See sections 110.22(B), 110.71, 210.19(B)(2), 215.2(B)(3), 240.86(A), 240.92(C)(1)(3), 240.100(A) for just a few examples of many locations where the NEC® requires an engineer to be involved.
If multiple overcurrent devices with different clearing times are used at the service, each overcurrent device will need to be labeled with its specific clearing time. This does not mean just taping the time-current curve chart to the service for the inspector to figure out.
The time-current curve chart provides many different clearing times based on the magnitude of the fault condition. The larger the fault, the faster the overcurrent device will operate which means a quicker clearing time.
Even though the code section allows the label to be field or factory applied, the actual clearing time is not known at the factory since it is a variable numeric value based on field installation conditions such as length, size and properties of the service entrance conductors. All of these characteristics have an impact on the final available fault current which is not known at the factory before the equipment is shipped out to the job site.
Item 4 is no big deal. Just mark the date the label is installed. This helps to date stamp the installation should any changes occur in the future.
Below is a preview of Article 110. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2017 NEC® edition of NFPA 70.
2014 Code Language:
110.16 Arc-Flash Hazard Warning. Electrical equipment, such as switchboards, switchgear, panelboards, industrial control panels, meter socket enclosures, and motor control centers, that are in other than dwelling units, and are likely to require examination, adjustment, servicing, or maintenance while energized, shall be field or factory marked to warn qualified persons of potential electric arc flash hazards. The marking shall meet the requirements in 110.21(B) and shall be located so as to be clearly visible to qualified persons before examination, adjustment, servicing, or maintenance of the equipment.
2017 Code Language:
110.16(A) General. Electrical equipment, such as switchboards, switchgear, panelboards, industrial control panels, meter socket enclosures, and motor control centers, that is in other than dwelling units, and is likely to require examination, adjustment, servicing, or maintenance while energized, shall be field or factory marked to warn qualified persons of potential electric arc flash hazards. The marking shall meet the requirements in 110.21(B) and shall be located so as to be clearly visible to qualified persons before examination, adjustment, servicing, or maintenance of the equipment.
110.16(B) Service Equipment. In other than dwelling units, in addition to the requirements in (A), a permanent label shall be field or factory applied to service equipment rated 1200 amps or more. The label shall meet the requirements of 110.21(B) and contain the following information:
(1) Nominal system voltage
(2) Available fault current at the service overcurrent protective devices
(3) The clearing time of service overcurrent protective devices based on the available fault current at the service equipment.
(4) The date the label was applied
Exception: Service equipment labeling shall not be required if an arc flash label is applied in accordance with acceptable industry practice.
Which of the following is required by the NEC to be marked on a 1600 amp electric service at a commercial occupancy?
Please register or sign in for electrical continuing education courses. If you were already signed in, your session probably expired, please sign back in. |