110.9 Interrupting Rating.

Overcurrent devices must have an interrupting rating at least equal to the current that is available at the line terminals. Passive devices like the lighting contactor just need to have an interrupt rating at least equal to the current they are interrupting.
Click to Enlarge
Overcurrent devices must have an interrupting rating at least equal to the current that is available at the line terminals. Passive devices like the lighting contactor just need to have an interrupt rating at least equal to the current they are interrupting.

Code Change Summary: Revisions were made regarding requirements for equipment interrupt ratings.

This code section addresses two different types of equipment and how they must be rated:

Before the electrician purchases or installs the items mentioned above, care should be taken to ensure that the equipment selected is properly rated for the current that must be interrupted. Overcurrent devices must have an interrupting rating at least equal to the current that is available at the line terminals. This is the maximum available fault current. For example, If it has been determined that there is 9,900 amps of available fault current at the line terminals of a 200 amp circuit breaker, using a breaker with a 10k AIC rating (10,000 amps interrupt capacity) complies with 110.9.

Devices that do not interrupt current at fault levels (switches and contactors) just need to have an interrupt rating at least equal to the current that needs to be interrupted. For example, to interrupt 30 amps of lighting load, use a contactor that is rated for at least 30 amps.

The code change to this section eliminates vague, subjective terminology. The previous code language required overcurrent devices to have an interrupting rating “sufficient for” the current that is available at the line terminals of the equipment. The new language states that overcurrent devices must have an interrupting rating “at least equal to” the current that is available at the line terminals of the equipment.

Below is a preview of Article 110. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2017 NEC® edition of NFPA 70.

2014 Code Language:

110.9 Interrupting Rating. Equipment intended to interrupt current at fault levels shall have an interrupting rating at nominal circuit voltage sufficient for the current that is available at the line terminals of the equipment.

Equipment intended to interrupt current at other than fault levels shall have an interrupting rating at nominal circuit voltage sufficient for the current that must be interrupted.

2017 Code Language:

110.9 Interrupting Rating. Equipment intended to interrupt current at fault levels shall have an interrupting rating at nominal circuit voltage at least equal to the current that is available at the line terminals of the equipment.

Equipment intended to interrupt current at other than fault levels shall have an interrupting rating at nominal circuit voltage at least equal to the current that must be interrupted.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

110.9 Interrupting Rating.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following circuit breakers can be used at a location in the wiring system where there is 38,000 amps of available fault current?

A: A 50 amp breaker with a 36k AIC rating.
B: A 50 amp breaker with a 42k AIC rating.
C: A 50 amp breaker with a 10k AIC rating.
D: A 50 amp breaker with a 22k AIC rating.