680.26(B)(2) Perimeter Surfaces.

Copper grids are permitted for equipotential bonding of perimeter surfaces adjacent to a pool.
Click to Enlarge

Copper grids are permitted for equipotential bonding of perimeter surfaces adjacent to a pool.

Copper bonding grids are often installed under perimeter surfaces around a pool to satisfy the equipotential bonding requirements in NEC® 680.26(B)(2).

When installing a copper bonding grid at unpaved portions of perimeter surfaces in accordance with NEC® 680.26(B)(2)(c)(2), the following rules must be followed:

a. At least one minimum 8 AWG bare solid copper or 40 percent copper-clad steel conductor is provided, including the 8 AWG copper equipotential bonding conductor, if available.

b. The conductor(s) follows the contour of the perimeter surface.

c. The conductor(s) is 450 mm to 600 mm (18 in. to 24 in.) from the inside walls of the pool.

d. The conductor(s) is under the unpaved portion of the perimeter surface 100 mm to 150 mm (4 in. to 6 in.) below finished grade.

e. The conductor(s) is installed only in perimeter surfaces not intended to have direct access to swimmers in the pool.

Below is a preview of the NEC®. See the full NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to NFPA 70.

2026 Code Language:

680.26(B)(2) Perimeter Surfaces. Bonding to perimeter surfaces shall be provided as specified in 680.26(B)(2)(a), 680.26(B)(2)(b), 680.26(B)(2)(c), and 680.26(B)(2)(d). The perimeter surface shall include unpaved surfaces, concrete, masonry pavers, and other types of paving. The perimeter surface to be bonded shall extend 3 feet horizontally beyond the inside walls of the pool at a height between 3 feet above and 3 feet below the maximum water level. Perimeter surfaces separated from the pool by a permanent wall or building 5 feet in height or more shall require equipotential bonding only on the pool side of the permanent wall or building.

c. Unpaved Portions of Perimeter Surfaces.

(2) A copper or 40 percent copper-clad steel conductor grid or unencapsulated steel structural welded wire reinforcement used for equipotential bonding of unpaved portions of perimeter surfaces shall meet the following:

a. It is installed in accordance with 680.26(B)(2)(a).

b. It is located within an unpaved surface(s) between 4 in. to 6 in. below finished grade.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

680.26(B)(2) Perimeter Surfaces.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is true for a copper grid under the perimeter surface adjacent to a pool?

A: The copper grid shall be constructed of 10 AWG stranded insulated copper.
B: The copper grid shall be constructed of 6 AWG stranded insulated copper.
C: The copper grid shall be constructed of 6 AWG solid insulated copper.
D: The copper grid must be located within an unpaved surface between 4 in. to 6 in. below finished grade.